D–EIMAC01905-23_00EN - 7/53
Safety valves can be provided with a changeover device as optional
Table 2 – Legend refrigerant circuit diagram (P&ID) – DUAL circuit units
HEAT EXCHANGER (BHPE) - HEAT RECOVERY OPTIONAL
PRESSURE RELIEF VALVE Pset = 25,5 bar
MICROCHANNEL CONDENSER COIL
DISCHARGE SHUT OFF ANGLE VALVE
DISCHARGE SHUT OFF BALL VALVE
HEAT EXCHANGER (BPHE) ECONOMIZER
SOLENOID VALVE (inside compressor)
ECONOMIZER ELECTRONIC EXPANSION VALVE
ELECTRONIC EXPANSION VALVE
PRESSURE RELIEF VALVE Pset = 15,5 bar
PRESSURE GAUGE (OPTIONAL)
ANTIVIBRATION JOINT * (only for XR/PR or Opt. 76b)
LIQUID RECEIVER (only with opt.01 THR)
HIGH PRESSURE SWITCH 22.7 bar
HIGH TEMPERATURE SWITCH (MOTOR THERMISTOR)
LOW PRESSURE LIMITER (CONTROLLER FUNCTION)
Water inlet and outlet are indicative. Please refer to the machine dimensional diagrams for exact water connections.
The series is composed by MONO (one circuit) and DUAL (two circuits) units.