Thermostatic control settings are accessible from Main PageThermostatic Control
Delta temperature respect the active setpoint to start the unit
(startup of first compressor)
Delta temperature respect the active setpoint to stop the unit
(shutdown of latest compressor)
Delta temperature respect the active setpoint to start a compressor
Delta temperature respect the active setpoint to stop a compressor
Minimum time between the compressors startup
Minimum time between the compressors shutdown
Unit standby period during Ice mode operation
4.7 Date/Time
The unit controller is able to take stored the actual date and time, that are used for:
1. Scheduler
2. Cycling of standby chiller with Master Slave configuration
3. Alarms Log
Date and time can be modified going in View/Set Unit Date/Time
Compressors start-up sequence - Cool mode