18 Technical data
Installation and operation manual
21
FAA71+100BUV1B
Split system air conditioner
3P654518-1A – 2021.03
3 Turn off main power supply.
4 Detach user interface from the master unit and connect it to the
slave unit.
Turn on the main power supply switch and set individual setting.
5 Perform field setting for slave unit.
6 Turn off the main power supply.
7 If there is more than one slave unit, repeat setting for each
8 Detach user interface from the slave unit, and reattach to the
master unit.
INFORMATION
You do not need to rewire the user interface from the
master unit if the optional remote controller for slave
unit is used. However, remove the wires attached to the
user interface terminal board of the master unit.
After the slave unit setting, remove the user interface
wiring, and rewire the user interface from the master
unit.
The unit does not operate properly when two or more
user interfaces are attached to the unit in the
simultaneous operation system mode.
Setting: Computerised control (forced OFF and ON/OFF
operation)
Wire specifications and how to perform wiring
Connect input from outside to terminals T1 and T2 of the terminal
block for user interface (there is no polarity).
F2 T1 T2
FORCED
OFF
a
a Input A
Wire specification
Wire specification Sheathed vinyl cord or cable (2 wire)
Gauge 0.75~1.25mm
2
External terminal Contact that can ensure the minimum
applicable load of 15VDC, 10mA.
Actuation
Forced OFF ON/OFF operation
Input „ON“ stops operation
(impossible by user inteface)
a) Input OFF → ON
Result: turns the unit ON
Input OFF enables control by
user interface
a) Input ON → OFF
Result: Turns the unit OFF
How to select FORCED OFF and ON/OFF OPERATION
1 Turn on the power and then use the user interface to select
operation.
2 Change setting:
If you want… Then
(1)
M SW
Forced OFF 12 (22) 1 01
ON/OFF operation 02
18 Technical data
A subset of the latest technical data is available on the regional
Daikin website (publicly accessible).
The full set of latest technical data is available on the Daikin
Business Portal (authentication required).
18.1 Wiring diagram
18.1.1 Unified wiring diagram legend
For applied parts and numbering, refer to the wiring diagram on the
unit. Part numbering is by Arabic numbers in ascending order for
each part and is represented in the overview below by "*" in the part
code.
Symbol Meaning Symbol Meaning
Circuit breaker Protective earth
Connection Protective earth (screw)
,
Connector
A
Rectifier
Earth Relay connector
Field wiring Short-circuit connector
Fuse Terminal
INDOOR
Indoor unit Terminal strip
OUTDOOR
Outdoor unit Wire clamp
Residual current
device
Symbol Colour Symbol Colour
BLK Black ORG Orange
BLU Blue PNK Pink
BRN Brown PRP, PPL Purple
GRN Green RED Red
GRY Grey WHT White
YLW Yellow
Symbol Meaning
A*P Printed circuit board
BS* Pushbutton ON/OFF, operation
switch
BZ, H*O Buzzer
C* Capacitor
AC*, CN*, E*, HA*, HE*, HL*,
HN*, HR*, MR*_A, MR*_B, S*, U,
V, W, X*A, K*R_*, NE
Connection, connector
D*, V*D Diode
DB* Diode bridge
DS* DIP switch
E*H Heater
FU*, F*U, (for characteristics,
refer to PCB inside your unit)
Fuse
(1)
Field settings are defined as follows:
M: Mode number – First number: for group of units – Number between brackets: for individual unit
SW: Setting number
—: Value number
: Default