English 23
11. TEST OPERATION
11-1 TO PERFORM A TEST RUN
CAUTION
This task is only applicable when using the BRC1E53 user interface. When using any other user interface,
see the installation manual or service manual of the user interface.
NOTE
Backlight. To perform an ON/OFF action on the user interface, the backlight does not need to be lit. For
any other action, it needs to be lit first. The backlight is lit for ±30 seconds when you press a button.
(1) Perform introductory steps.
Table 13
(2) Start the test run.
Table 14
(3) Check operation for 3 minutes.
(4) Check operation of the airflow direction.
#
Action
1
Open the liquid stop valve (A) and gas stop valve (B) by removing the stem cap and turning counter-
clockwise with a hex wrench until it stops.
2 Close the service cover to prevent electric shocks.
3 Turn On power for at least 6 hours before starting operation to protect the compressor.
4 On the user interface, set the unit to cooling operation mode.
# Action Result
1 Go to the home menu
2
Press at least 4 seconds.
The Service Setting menu is displayed.
3
Select the Test Operation.
4
Press.
Test Operation is displayed on the home menu.
5
Press within 10 seconds.
Test run starts.
AB
Cool
Set to
28
°C
Return Setting
Service Settings 1/3
Test Operation
Maintenance Contact
Field Settings
Demand
Min Setpoints Differential
Group Address
Cool
Return Setting
Test Operation
4PEN468968-1C.book Page 23 Friday, March 24, 2017 1:30 PM