Field Setting from Outdoor Unit PCB ESIE15-13B
88 Field Setting
3.2.5 List of Contents of Retry and Error
Take the following steps to check contents of retry and error.
k: ON h: OFF l: BLINK
Error
code
Contents of retry or malfunction
Confirmation 1 Confirmation 2 Confirmation 3
HAP H1P H2P H3P H4P H5P H6P H7P HAP H1P H2P H3P H4P H5P H6P H7P HAP H1P H2P H3P H4P H5P H6P H7P
C4 Indoor heat exchanger thermistor llkhhhlhllkhhlhhllkkhhhh
E1 Faulty outdoor unit PCB llhkhhllllkhhhhlllkkhhhh
E3 Abnormal high pressure llkhhhllllkkhhhh
E4 Abnormal low pressure llkhhlhhllkkhhhh
E5 Compressor motor lock llkhhlhlllkkhhhh
E7
Abnormal outdoor
fan motor
DC motor 1 lock llkhhlllllkkhhhl
DC motor 2 lock llkkhhlh
Abnormal inverter transmission llkkhhll
E9
Abnormal electronic
expansion valve
Disconnected electronic expansion valve connector
llkhlhhlllkkhhhl
Malfunction due to wet conditions llkkhhlh
F3
Abnormal discharge
pipe temperature
Abnormal discharge pipe temperature
llhkhlhlllkhhhllllkkhhhl
Disconnected discharge pipe thermistor
llkkhhlh
H3 Abnormal high pressure switch llhkhlhhllkhhhllllkkhhhh
H9 Abnormal outdoor air thermistor llkhlhhlllkkhhhh
J1 Abnormal pressure sensor llhkhllhllkhhhhlllkkhhhh
J3 Abnormal discharge pipe thermistor llkhhhllllkkhhhh
J5 Abnormal suction pipe thermistor llkhhlhlllkkhhhh
J6 Abnormal heat exchanger distributor pipe thermistor llkhhllhllkkhhhh
J7 Abnormal intermediate heat exchanger thermistor llkhhlllllkkhhhh
J8 Abnormal liquid pipe thermistor llkhlhhhllkkhhhh
L1 PCB failure llhkhlllllkhhhhlllkkhhhh
L4 Elevated radiation fin temperature llkhhlhhllkkhhhh
L5 Compressor instantaneous overcurrent llkhhlhlllkkhhhh
L8 Compressor overload llkhlhhhllkkhhhh
L9 Compressor lock llkhlhhlllkkhhhh
LC
Abnormal transmission (between the control and the inverter)
llkhllhhllkkhhhh
P1 Unbalanced power supply voltage llhklhhhllkhhhhlllkkhhhh
P4 Abnormal radiation fin thermistor llkhhlhhllkkhhhh
PJ Faulty capacity setting llkhllhlllkkhhhh
U0
Abnormal
refrigerant
shortage
Refrigerant shortage warning llhklhhlllkhhhhhllkkhhhl
Abnormal refrigerant shortage
llkkhhlh
U2
Abnormal power
supply voltage
Inverter undervoltage and overvoltage llkhhhlhllkkhhhl
SP-PAM overvoltage llkkhhlh
U4
Abnormal transmission (between indoor and outdoor units)
llkhhlhhllkkhhhh
UA Faulty field setting switch llkhlhlhllkkhhhh
UF Improper piping and improper communication wiring llllllkkhhhh
To enter "Monitor mode," press the MODE (BS1)
button when in "Setting mode 1."
Press the SET (BS2) button to set the LED
display to retry or error item.
When the RETURN (BS3) button is pressed, the
LED display for RETURN 1 turns ON.
<Selection of retry or error item>
When SET (BS2) button is pressed, the LED
display for RETURN 2 turns ON.
<Display of RETURN 2>
When SET (BS2) button is pressed, the LED
display for RETURN 3 turns ON.
Press the RETURN (BS3) button to return the
system to the initial state of "Monitor mode."
Pressing the MODE (BS1) button will bring the
system to the "Setting mode 1."
<Display of RETURN 3>
<Display of RETURN 1>

Table of Contents

Other manuals for Daikin FAQ100CVEB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FAQ100CVEB and is the answer not in the manual?

Daikin FAQ100CVEB Specifications

General IconGeneral
BrandDaikin
ModelFAQ100CVEB
CategoryAir Conditioner
LanguageEnglish

Related product manuals