EasyManuals Logo

Daikin FAQ100CVEB Service Manual

Daikin FAQ100CVEB
215 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #143 background imageLoading...
Page #143 background image
ESIE15-13B Troubleshooting by Remote Controller
Service Diagnosis 129
4.8 Transmission Error (between Indoor Unit PCB and
Adaptor PCB)
Remote
Controller
Display
C1
Applicable
Models
FCQG
Method of Error
Detection
Check the condition of transmission between indoor unit PCB (A1P) and adaptor PCB using
micro-computer.
Error Decision
Conditions
When normal transmission is not conducted for certain duration (15 seconds or more). After 60
seconds, error is display on the remote controller.
Supposed
Causes
Connection defect of the connector indoor unit PCB (A1P) and adaptor PCB
Defective indoor unit PCB (A1P)
Defective adaptor PCB
External factor (Noise, etc.)

Table of Contents

Other manuals for Daikin FAQ100CVEB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FAQ100CVEB and is the answer not in the manual?

Daikin FAQ100CVEB Specifications

General IconGeneral
BrandDaikin
ModelFAQ100CVEB
CategoryAir Conditioner
LanguageEnglish

Related product manuals