EasyManuals Logo

Daikin FAQ100CVEB Service Manual

Daikin FAQ100CVEB
215 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #171 background imageLoading...
Page #171 background image
ESIE15-13B Troubleshooting by Remote Controller
Service Diagnosis 157
4.24 Radiation Fin Temperature Rise
Remote
Controller
Display
L4
Applicable
Models
RZQG
Method of Error
Detection
Radiation fin temperature is detected by the radiation fin thermistor.
Error Decision
Conditions
When the temperature of the inverter radiation fin rises abnormally due to faulty heat
dissipation.
Supposed
Causes
Actuation of fin thermal switch
Insufficient cooling of inverter radiation fin
High outdoor air temperature
Blocked suction inlet
Blocked discharge outlet
Dirty radiation fin
Disconnection of connector
Defective radiation fin thermistor
Defective outdoor unit inverter PCB

Table of Contents

Other manuals for Daikin FAQ100CVEB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FAQ100CVEB and is the answer not in the manual?

Daikin FAQ100CVEB Specifications

General IconGeneral
BrandDaikin
ModelFAQ100CVEB
CategoryAir Conditioner
LanguageEnglish

Related product manuals