3.2.19 Low Outdoor Air Temperature Control in Cooling Operation
Controls compressor and outdoor unit fan under low outdoor air temperature condition to secure
pressure difference between high and low pressure.
Hp: High pressure
Lp: Low pressure
Ta: Outdoor air temperature
Tfin: Inverter fin temperature
Frequency Restriction
Normal operation
Outdoor unit fan: Stop
Compression ratio < 2.1
Compressor operation frequency
restriction (refer to the followings)
Hp-Lp < 0.93MPa
Hp-Lp < 0.78MPa
Hp-Lp < 0.78MPa
Compression ratio < 1.8
Compression ratio < 1.8
Hp < 1.86MPa
Tfin < 66°C
OR
OR
OR
&
&
&
Compression ratio > 2.4
Hp-Lp > 1.08MPa
Ta > 27°C
OR
OR
Hp < 1.57MPa
Ta < 25°C
Hp < 1.57MPa
Hp < 2.94MPa
Hp-Lp > 0.88MPa
Compression ratio > 2.0
Hp > 1.66MPa
&
OR
Tfin ≥ 81°C
Hp-Lp > 0.98MPa
Compression ratio > 2.2
Hp > 2.25MPa
&
OR
Outdoor unit fan
-1 step/90 sec.
Outdoor unit fan
+1 step/90 sec.
Outdoor unit fan
Step 1
Lower limit frequency
Step 11
RZQG71L
Upper limit frequency
Step 17
Lower limit frequency
Step 11
RZQG100-140L
Upper limit frequency
Step 17
No frequency
restriction
Ta ≤ 25°C
Ta > 27°C