(2) Make sure the drain piping works properly.
After drain piping work is complete, perform a drain-
age check by opening the front panel, removing the
air lter, pouring water into the drain pan, and making
sure water ows smoothly out of the drain hose.
(Refer to Fig. 19)
Plastic container
for pouring
Drain pan
Make sure not to splash the water.
Fig. 19
CAUTION
Drain piping connections
Do not connect the drain piping directly to sewage pipes
that smell of ammonia. The ammonia in the sewage might
enter the indoor unit through the drain piping and corrode
the heat exchanger.
Keep in mind that it will block the drain pipe and cause
water to collect.
7. ELECTRIC WIRING WORK
7-1 GENERAL INSTRUCTIONS
All eld supplied parts and materials and electric works
must conform to local codes.
Use copper wire only.
For electric wiring work, refer to also “WIRING DIAGRAM”
attached to the unit.
For details of remote controller wiring, refer to the installa-
tion manual attached to the remote controller.
All wiring must be performed by an authorized electrician.
A circuit breaker capable of shutting down power supply to
the entire system must be installed.
Refer to the installation manual attached to the outdoor
unit for the size of power supply wiring connected to the
outdoor unit, the capacity of the circuit breaker and switch,
and wiring instructions.
Be sure to ground the air conditioner.
DANGER
Do not ground units to water pipes, telephone wires or
lightning rods because incomplete grounding could cause
a severe shock hazard resulting in severe injury or death,
and to gas pipes because a gas leak could result in an
explosion which could lead to severe injury or death.
7-2 ELECTRICAL CHARACTERISTICS
Units Power supply Fan motor
Model Hz Volts
Voltage
range
MCA MOP W FLA
FAQ18TAVJU
60 208/230
Max. 253
Min. 187
0.5 15 43 0.4
FAQ24TAVJU
0.6 15 43 0.5
MCA: Minimum Circuit Ampacity (A)
MOP: Maximum Overcurrent Protective Device (A)
W: Fan Motor Rated Output (W)
FLA: Full Load Ampere (A)
7-3 SPECIFICATIONS FOR FIELD SUPPLIED
FUSES AND WIRE
Model
Power supply wiring
Remote controller wiring
Transmission wiring
Fuse
Size Wire Size
FAQ18TAVJU
15A
Wiring size
and length
must
comply
with local
codes.
2-conductor,
stranded
non-shielded
copper cable
PVC/vinyl
jacket
(NOTE)
AWG18-16
(0.75-
1.25 mm
2
)
FAQ24TAVJU
Allowable lengths of transmission wiring and remote controller
wiring are as follows.
(1) Outdoor unit – Indoor unit:
Max. 3280 ft (1,000 m)
(2) Indoor unit – Remote controller:
Max. 1640 ft (500 m)
NOTE
Vinyl cord with sheath or cable (Insulated thickness :
1/16in. (1 mm) or more)