14
English
9. FIELD SETTING
〈Field settings may have to be performed using the
remote controller, depending on the type of installation.〉
(1) Make sure the control box covers are closed on the
indoor and outdoor units.
(2) Depending on the type of installation, make the eld
settings from the remote controller after the power is
turned on, following the installation manual attached
to the remote controller.
• The settings can select “Mode No.”, “FIRST CODE
NO.” and “SECOND CODE NO.”.
• The “Field Settings” included with the remote control-
ler lists the order of the settings and method of opera-
tion.
0
Unit No.
1
–
01
5
–––
9
–––
2
–
02
6
–––
a
–––
3
–
01
7
–––
b
–––
Field Settings
0
–
01
4
–––
8
–––
Setting
Mode
20
SECOND CODE NO.
FIRST CODE NO.
Mode No.
FIELD SET MODE
Fig. 29
• Lastly, make sure the customer keeps the installation
manual, along with the operating manual, in a safe place.
〈When using wireless remote controllers〉
• When using wireless remote controllers, wireless remote
controller address setting is necessary. Refer to the instal-
lation manual attached to the wireless remote controller
for setting instructions.
9-1 SETTING FILTER SIGN
• Remote controllers are equipped with display air lter
signs to display the time to clean air lters.
• Change the SECOND CODE NO. according to Table 2
depending on the amount of dirt or dust in the room.
(SECOND CODE NO. is factory set to “01” for air lter
contamination-light)
Table 2
Setting
Spacing time of
display air lter
sign
Mode
No.
FIRST
CODE
NO.
SECOND
CODE
NO.
Air lter contami-
nation-light
Approx. 200hours
20 0
01
Air lter contami-
nation-heavy
Approx. 100hours 02
9-2 SETTING AIRFLOW RATE INCREASE MODE
• It is possible to raise set airow (HIGH and LOW) from the
eld. Change the SECOND CODE NO. as shown in
Table3 to suit your needs.
(SECOND CODE NO. is factory set to “01” for Standard.)
Table 3
Setting Mode No.
FIRST
CODE NO.
SECOND
CODE NO.
Standard
23 0
01
A little increase 02
Increase 02
9-3 REMOTE CONTROL SETTING
• Forced off and ON/OFF operation should be selected by
selecting the SECOND CODE NO. as shown in Table 4.
Table 4
External ON/OFF input Mode No.
FIRST
CODE NO.
SECOND
CODE NO.
Forced off
22 1
01*
ON/OFF operation 02
* Factory set
• Input A of forced off and ON/OFF operation work as
shown in Table 5.
Table 5
Forced off ON/OFF operation
Input A “on” to force a stop
(remote controller reception
prohibited)
Unit operated by changing input
A from “off” to “on”
Input A “off” to allow remote
controller
Unit stopped by changing input
A from “on” to “off”
01_EN_3PN07521-5H.indd 14 7/9/2018 14:13:36