Daikin FAQ18TAVJU - 8. Wiring Example and Remote Controller Setup (Continued); Remote Controller Wiring Configurations

Daikin FAQ18TAVJU
17 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
13
English
1. When using 1 remote controller (Normal operation)
L1L2
IN/D OUT/D
F
1 F2 F1 F2
P
1
P
2
P
1
P
2
F
1
F
2
T
1
T
2
Control box
Power Supply
208/230V
1~ 60Hz
Outdoor unit
Indoor unit
Remote
controller
L
1
L
2
Fig. 25
2. When using 2 remote controllers
Fig. 26
P
1
P
2
P
1
P
2
L1L2
IN/D OUT/D
F
1 F2 F1 F2
P
1
P
2
F
1
F
2
T
1
T
2
Control box
For use with
2 remote
controllers
Power Supply
208/230V
1~ 60Hz
Outdoor unit
Indoor unit
L
1
L
2
[ PRECAUTIONS ]
1. Do not ground the equipment on gas pipes, water pipes
or lightning rods, or crossground with telephones.
Improper grounding could result in electric shock.
2. The remote controller wiring (P
¹
and P
²
) and transmis-
sion wiring (F
¹
and F
²
) have no polarity.
8-3 CONTROL BY 2 REMOTE
CONTROLLERS (Controlling 1 indoor unit by 2
remote controllers)
When using 2 remote controllers, one must be set to
“MAIN” and the other to “SUB”.
Main/sub changeover
Refer to the installation manual supplied with the remote
controller.
Wiring method
(1) Remove the control box cover.
(2) Add the remote controller 2 (SUB) to the terminal block
for remote controller (P
¹
, P
²
) in the control box. (There is
no polarity.)
Remote controller wiring
terminal block
Remote
controller 2
(SUB)
Remote
controller 1
(MAIN)
1
P
2
P
1
F
2
F
1
T
2
T
FORCED
OFF
REMOTE
CONTRL
TRANSMISSION
WIRING
Fig. 27
8-4 REMOTE CONTROL (FORCED OFF AND ON/
OFF OPERATION)
Connect input lines from the outside to the terminals T
¹
and T
²
on the terminal block (6P) for remote controller to
achieve remote control.
See “9. FIELD SETTING for details on operation.
Input A
1
P
2
P
1
F
2
F
1
T
2
T
FORCED
OFF
REMOTE
CONTRL
TRANSMISSION
WIRING
Fig. 28
Wire specication Sheathed vinyl cord or 2 core cable
Gauge AWG18 – 16 (0.75-1.25 mm
2
)
Length Max. 328 ft. (100 m)
External terminal
Contact that can ensure the minimum
applicable load of 15 V DC, 1 mA.
8-5 CENTRALIZED CONTROL
For centralized control, it is necessary to designate the
group No. For details, refer to the manual of each optional
controllers for centralized control.
01_EN_3PN07521-5H.indd 13 7/9/2018 14:13:36