25
Engineering & Physical Data
MODEL
INDOOR FCQN100EXV1
OUTDOOR RQ90DXV1 RQ100DXV1 RQ100DXY1
SAFETY
DEVICE
HIGH PRESSURE
SWITCH
TYPE NC
OPEN kPa / psi 4140 / 600.46
CLOSE kPa / psi 3310 / 480.07
LOW PRESSURE
SWITCH
TYPE NC
OPEN kPa / psi 48 / 6.96
CLOSE kPa / psi 152 / 22.05
PHASE SEQUENCER N/A YES
DISC. THERMOSTAT SETTING °C / F N/A 130 / 266
MODEL
INDOOR FCQN125EXV1
OUTDOOR RQ125DXY1
SAFETY
DEVICE
HIGH PRESSURE
SWITCH
TYPE NC
OPEN kPa / psi 4140 / 600.46
CLOSE kPa / psi 3310 / 480.07
LOW PRESSURE
SWITCH
TYPE NC
OPEN kPa / psi 48 / 6.96
CLOSE kPa / psi 152 / 22.05
PHASE SEQUENCER YES
DISC. THERMOSTAT SETTING °C / F 130 / 266
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.