13
Application Information
3) Cable Size
Cooling only
Model Unit
FFRN25/35CXV1 FFRN50CXV1 FCRN50EXV1
RN25/35CXV1 RN50CXV1 RN50CXV1
Power supply cable size
Number of wire
mm²
1.5
3
2.5
3
2.5
3
Interconnection cable size
Number of wire
mm²
1.5
3
2.5
3
2.5
3
Recommended fuse A 15 20 13
Model Unit
FCRN60EXV1 FCRN71EXV1 FCRN100EXV1
RN60CXV1 RR71CXV1 RR90DXV1
Power supply cable size
Number of wire
mm
2
2.5
3
4.0
3
4.0
3
Interconnection cable size
Number of wire
mm
2
2.5
3
2.5
3
2.5
4
Recommended fuse A 18 25 25
Model Unit
FCRN100EXV1 FCRN100EXV1 FCRN125EXV1
RR100DXV1 RR100DXY1 RR125DXY1
Power supply cable size
Number of wire
mm
2
4.0
3
2.5
5
4.0
5
Interconnection cable size
Number of wire
mm
2
2.5
4
1.5
4
1.5
4
Recommended fuse A 30 13 18
Heatpump
Model Unit
FFQN25/35CXV1 FFQN50CXV1 FCQN50EXV1
RYN25/35CXV1 RYN50CXV1 RYN50CXV1
Power supply cable size
Number of wire
mm
2
1.5
3
2.5
3
2.5
3
Interconnection cable size
Number of wire
mm
2
1.5
5
2.5
5
2.5
5
Recommended fuse A 15 20 13
Model Unit
FCQN60EXV1 FCQN71EXV1 FCQN100EXV1
RYN60CXV1 RQ71CXV1 RQ90DXV1
Power supply cable size
Number of wire
mm
2
2.5
3
4.0
3
4.0
3
Interconnection cable size
Number of wire
mm
2
2.5
5
2.5
5
2.5
3 & 4
Recommended fuse A 18 25 25
Model Unit
FCQN100EXV1 FCQN100EXV1 FCQN125EXV1
RQ100DXV1 RQ100DXY1 RQ125DXY1
Power supply cable size
Number of wire
mm
2
4.0
3
2.5
5
2.5
5
Interconnection cable size
Number of wire
mm
2
2.5
3 & 4
1.5
3 & 4
1.5
3 & 4
Recommended fuse A 30 13 18
DAIKIN_FFRN.indb 13DAIKIN_FFRN.indb 13 12/27/2012 9:28:09 AM12/27/2012 9:28:09 AM