EasyManua.ls Logo

Daikin FCRN60EXV1 - High Capacity Model Data

Daikin FCRN60EXV1
73 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
23
Engineering & Physical Data
Engineering Data - R410A MODEL
MODEL
INDOOR UNIT FCRN100EXV1 FCRN125EXV1
OUTDOOR UNIT RR90DXY1 RR100DXV1 RR125DXY1
NOMINAL COOLING CAPACITY
Btu/h 31000 39000 45000
W 9086 11430 13190
NOMINAL TOTAL INPUT POWER (COOLING) W 2770 3920 4390
NOMINAL RUNNING CURRENT (COOLING) A 5.20 17.90 7.80
EER W/W 3.28 2.92 2.87
REFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR CAPILLARY TUBE
REFRIGERANT CHARGE kg 2.60 2.10 2.25
MODEL
INDOOR UNIT FCQN100EXV1 FCQN125EXV1
OUTDOOR UNIT RQ90DXY1 RQ100DXV1 RQ125DXY1
NOMINAL COOLING CAPACITY
Btu/h 31000 39000 45000
W 9086 11430 13190
NOMINAL HEATING CAPACITY
Btu/h 33400 39000 48000
W 9789 11430 14070
NOMINAL TOTAL INPUT POWER (COOLING) W 2770 3920 4390
NOMINAL TOTAL INPUT POWER (HEATING) W 2550 3740 4010
NOMINAL RUNNING CURRENT (COOLING) A 5.2 17.9 7.8
NOMINAL RUNNING CURRENT (HEATING) A 5.00 17.30 7.30
EER W/W 3.28 2.92 2.87
COP W/W 3.84 3.06 3.46
REFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR CAPILLARY TUBE
REFRIGERANT CHARGE kg 2.60 2.10 2.25
POWER SOURCE V/Ph/Hz 220 - 240 /1/50 220 - 240 /1/50 380 - 415 / 3 / 50
REFRIGERANT TYPE R410A
INDOOR UNIT
CONTROL
AIR DISCHARGE 4 WAY AUTOMATIC LOUVER (UP & DOWN)
OPERATION WIRELESS MICROCOMPUTER REMOTE CONTROL
AIR FLOW
HIGH l/s / CFM 490 / 1030 570 / 1200
MEDIUM l/s / CFM 410 / 860 490 / 1030
LOW l/s / CFM 350 / 740 440 / 930
SUPER LOW l/s / CFM 295 / 620 370 / 780
SOUND PRESSURE LEVEL (H/M/L/SL) dBA 47 / 44 / 40 / 36 49 / 45 / 43 / 39
UNIT DIMENSION [Panel] HEIGHT X WIDTH X DEPTH mm 300 X 820 X 820 [375 X 990 X 990]
PACKING DIMENSION HEIGHT X WIDTH X DEPTH mm 335 X 916 X 916
UNIT WEIGHT (UNIT + PANEL) kg 42 + 6
CONDENSATE DRAIN SIZE mm 19.05
FAN
TYPE BLOWER WHEEL
DRIVE DIRECT
FAN MOTOR
TYPE INDUCTION
INDEX OF PROTECTION (IP) IP20
INSULATION GRADE CLASS B
RATED INPUT POWER W 176 176 221
RATED RUNNING CURRENT A 0.79 0.79 0.97
MOTOR MAX OUTPUT W 60 100
POLES 6
COIL
TUBE
MATERIAL SEAMLESS INNER GROOVE COPPER
DIAMETER mm 7
FIN
MATERIAL ALUMINIUM (SLIT FIN)
FACE AREA m
2
0.461 0.464
ROW 3
AIR QUALITY FILTER
TYPE WASHABLE SARANET FILTER
QUANTITY pc 1
CASING COLOUR WITHOUT PAINT
AIR FLOW I/s / CFM 1605 / 3400 2171 / 4600
OUTDOOR UNIT
SOUND PRESSURE LEVEL dBA 58 60
UNIT DIMENSION HEIGHT X WIDTH X DEPTH mm 852 X 1030 X 400
PACKING DIMENSION HEIGHT X WIDTH X DEPTH mm 1010 x 1180 x 514
UNIT WEIGHT (RN / RYN) kg 86 95 98
PIPE
CONNECTION
TYPE FLARE VALVE
SIZE
LIQUID mm 9.52
GAS mm 15.88
FAN
TYPE PROPELLER
DRIVE DIRECT
FAN MOTOR
TYPE INDUCTION
INDEX OF PROTECTION (IP) N / A N / A IP20
INSULATION GRADE CLASS B CLASS B CLASS F
RATED INPUT POWER W 257 257 276
RATED RUNNING CURRENT A 1.1 1.1 1.34
MOTOR OUTPUT W 145
POLES 8
COMPRESSOR
TYPE SCROLL
OIL TYPE MOBIL EAL ARCTIC 22C
OIL AMOUNT cm
3
1242 1951 1656
RN RATED INPUT POWER W 2337 3487 3893
RYN
RATED INPUT POWER
(COOLING)
W 2337 3487 3893
RATED INPUT POWER
(HEATING)
W 2117 3307 3513
RATED RUNNING CURRENT A 4.57 16 7.03
RATED RUNNING CURRENT
(COOLING)
A 4.57 16 7.03
RATED RUNNING CURRENT
(HEATING)
A 4.37 15.40 6.53
LOCKED ROTOR AMP. A 48 136 74
COIL
TUBE
MATERIAL SEAMLESS INNER GROOVE COPPER
DIAMETER (RN/RYN) mm 777
FIN
MATERIAL ALUMINIUM (CORR.FIN)
FACE AREA m
2
0.87
ROW 2
CASING COLOUR LIGHT GREY
ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 (NON-DUCTED UNIT) OR ISO 13253 (DUCTED UNIT).
COOLING HEATING
INDOOR: 27°C DB/ 19°C WB INDOOR: 20°C DB
OUTDOOR: 35°C DB/ 24°C WB OUTDOOR: 7°C DB/ 6°C WB
DAIKIN_FFRN.indb 23DAIKIN_FFRN.indb 23 12/27/2012 9:28:10 AM12/27/2012 9:28:10 AM