EasyManua.ls Logo

Daikin FDR200FRY16 - User Manual

Daikin FDR200FRY16
27 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
3P724053-1A
FDMR36ERV16
FDR65FRV16
FDR100FRV16
FDR130FRV16
FDR130FRV162
FDR200FRY16
FD65DSV16
FD100DSV16
FD130DSV16
FD200DSY16
FD60GRV16
FD90GRV16
FD120GRV16
FD180GRY16
OPERATION
Question and Answer IconNeed help?

Do you have a question about the Daikin FDR200FRY16 and is the answer not in the manual?

Summary

Safety Precautions

Warning Precautions

Important safety warnings for installation and maintenance personnel.

Caution Precautions

Important safety cautions regarding installation and operation procedures.

Indoor Unit Installation

Mounting Guidelines

Guidelines for securely mounting the indoor unit, considering weight and alignment.

Drain Piping Work

Procedures and recommendations for installing the drain piping for concealed units.

Outdoor Unit Installation

Refrigerant Piping Guidelines

Maximum Pipe Length and Bends

Recommendations for refrigerant pipe length and maximum number of bends for system performance.

Electrical Connection

Wiring Specifications

Information on power supply cable size, interconnection cable size, and recommended fuses.

Vacuuming and Charging

Vacuuming Procedure

Steps for performing system evacuation to remove moisture and air before charging.

Charging Procedure

Guidelines for charging the system with the correct type and amount of refrigerant.

System Refrigerant Charge Level Guidelines

Table specifying refrigerant charge amounts based on indoor/outdoor unit combinations.

Special Precautions for Scroll Compressors

Charging Procedures for Single Phase Compressors

Specific charging procedures and precautions for single-phase scroll compressor units.

Charging Procedures for Three Phase Compressors

Specific charging procedures and precautions for three-phase scroll compressor units.

Service and Maintenance

Troubleshooting

Fault Diagnosis and Solutions

List of common faults, their causes, and suggested actions for troubleshooting.

Summary

Safety Precautions

Warning Precautions

Important safety warnings for installation and maintenance personnel.

Caution Precautions

Important safety cautions regarding installation and operation procedures.

Indoor Unit Installation

Mounting Guidelines

Guidelines for securely mounting the indoor unit, considering weight and alignment.

Drain Piping Work

Procedures and recommendations for installing the drain piping for concealed units.

Outdoor Unit Installation

Refrigerant Piping Guidelines

Maximum Pipe Length and Bends

Recommendations for refrigerant pipe length and maximum number of bends for system performance.

Electrical Connection

Wiring Specifications

Information on power supply cable size, interconnection cable size, and recommended fuses.

Vacuuming and Charging

Vacuuming Procedure

Steps for performing system evacuation to remove moisture and air before charging.

Charging Procedure

Guidelines for charging the system with the correct type and amount of refrigerant.

System Refrigerant Charge Level Guidelines

Table specifying refrigerant charge amounts based on indoor/outdoor unit combinations.

Special Precautions for Scroll Compressors

Charging Procedures for Single Phase Compressors

Specific charging procedures and precautions for single-phase scroll compressor units.

Charging Procedures for Three Phase Compressors

Specific charging procedures and precautions for three-phase scroll compressor units.

Service and Maintenance

Troubleshooting

Fault Diagnosis and Solutions

List of common faults, their causes, and suggested actions for troubleshooting.

Overview

This document serves as an installation and operation manual for Daikin ceiling-concealed split-type air conditioners. It provides comprehensive guidelines to ensure safe, efficient, and proper functioning of the appliance. The manual is intended for use by expert and trained users in various settings, including shops, light industry, farms, and commercial environments.

Safety Precautions

The manual emphasizes critical safety precautions for both installation and maintenance. It highlights that all installation and maintenance tasks must be performed by qualified personnel familiar with local codes and regulations. Proper electrical wiring, in accordance with national wiring regulations, is paramount, and the unit must be grounded to prevent electrical hazards. The importance of installing an earth leakage breaker is stressed to prevent electric shocks or fire.

Users are warned against touching refrigerant piping or moving fan parts with electrical wiring. Before any servicing or installation, the unit must be switched off and disconnected from the main power supply. Pulling the power cord while the unit is on is strictly prohibited due to the risk of electric shocks and fire. To prevent interference, indoor and outdoor units, power cables, and transmission wiring should be kept at least 1 meter away from TVs and radios.

Several cautions are also provided:

  • The unit should not be installed where flammable gas leaks may occur, as this could lead to fire.
  • Proper drainage piping connection is essential to prevent water leakage and damage to furniture.
  • Overcharging the unit is prohibited, as it can cause over-current or damage to the compressor.
  • Panels must be securely closed after service or installation to prevent noisy operation.
  • Sharp edges and coil surfaces pose injury hazards, and contact with these areas should be avoided.
  • Before turning off the power supply, the remote controller's ON/OFF switch should be set to "OFF" to prevent the fans from starting automatically when power resumes, which could be hazardous.
  • Units should not be installed near doorways or in rooms where mineral oil, oil vapor, or oil steam exist, as this can cause plastic parts to melt or deform.
  • In kitchen installations, flour should be kept away from the unit's suction.
  • The unit is not suitable for factory use where cutting oil mist, iron powder, or significant voltage fluctuations are present.
  • Installation in areas with sulphide gas, such as hot springs or oil refinery plants, is not recommended.
  • The color of wires and terminal markings of the outdoor unit must match those of the indoor unit.
  • The air conditioner unit should not be installed or used in a laundry room.
  • Joined and twisted wires should not be used for incoming power supply.

Refrigerant Information

The system uses R410A/R22 refrigerant, requiring strict precautions to keep the system clean, dry, and tightly sealed. Impurities, including SUNISO oil, other mineral oils, and moisture, must be kept out. The system must be kept tight during installation. R410A is a mixed refrigerant that does not contain chlorine, does not destroy the ozone layer, and contributes only slightly to the greenhouse effect if released. Additional R410A refrigerant must be charged in its liquid state; charging in gaseous state can lead to composition changes and abnormal system function. The design pressure of the system is 4.17MPa.

Installation of the Indoor Unit

The indoor unit must be mounted on strong overhead supports, ensuring it can bear the unit's weight. Hanger rods should be aligned and securely fastened, and the fan-coil unit's base must be level in both horizontal directions, accounting for the recommended gradient for drainage flow. Clearances for servicing and optimal airflow are specified, and the unit should be positioned to prevent short-circuiting of cool discharge air. Direct sunlight on the unit should be avoided, and the location should be suitable for piping and drainage, with ample distance from doors.

During brazing of liquid and gas pipes for the indoor unit, a wet cloth should be used to prevent insulation burning, and insulation must be applied after brazing. M10/M12 rods should be used for installation, with the number of rods corresponding to the number of hanger metals provided.

Ceiling Concealed Drain Piping Work

Drain piping must be installed as shown in the diagram to prevent leaks and condensation. Piping should be as short as possible and slanted to improve flow, with the unit tilted between 10 to 15mm. The drain pipe slope should be at least 1:100. Secure insulation of the drain pipe is crucial. A drain trap must be provided at the drain outlet to relieve pressure differences between the unit and the outside atmosphere, preventing splashes or odors. Pipes should be kept straight for easy cleaning and to prevent dirt accumulation. A water drainage test must be conducted after installation to ensure smooth flow. In humid environments, an extra drain pan covering the entire indoor unit area is recommended.

Installation of the Outdoor Unit

The outdoor unit should be installed to prevent discharged air from being drawn back in (short-circuiting). Sufficient space for maintenance around the unit is required. The coolest possible location should be chosen, where intake air does not exceed 48°C. Obstructions to airflow must be removed. When multiple outdoor units are installed, they must be positioned to prevent one unit from drawing in the discharge air of another, whether side-by-side or stacked. All units should face the same or opposite directions to avoid short-circuiting. The location must be well-ventilated, capable of bearing the unit's weight, and isolating noise and vibration. Protection from direct sunlight (e.g., an awning) is advisable. Smooth drainage of rainwater and defrost water is necessary, and the unit should not be buried in snow or exposed to strong winds. The location should not annoy neighbors with air discharge or operating sound levels, and it should not be susceptible to dust or oil mist.

Operating the condensing unit in atmospheres containing oils (including machine oils), salt (coastal areas), or sulphide gas (near hot springs, oil refinery plants) can lead to unit failure.

Installation Clearance

Guidelines for installation clearance are provided for various outdoor unit models (RR36ERY16, RR65FRY16, R65DSY16, R60GRY16, RR100FRY16, R100DSY16, R90GRY16, RR130FRY16, R130DSY16, R120GRY16) to prevent hot air short-circuiting when multiple units are installed. Specific dimensions (A, B, C, D) are given for horizontal air discharge configurations.

Optional Accessories

A table lists compatible wired and optional wireless remote controllers for various indoor unit models. The wireless remote is optional and can be used with the IR sensor provided in the wired remote, which comes as an accessory with indoor units.

Refrigerant Piping

The manual details maximum pipe length and number of bends. Excessive pipe length or bends can reduce capacity and reliability, potentially leading to compressor failure. The shortest path is always recommended. Field piping arrangements require liquid loops or oil traps based on the relative positions of indoor and outdoor units. A field-supplied sight glass must be assembled and mounted as shown in the figure. The guarantee on performance is revoked if piping height, length, or number of bends exceed specified limits. Bends must be made carefully to avoid crushing the pipe, using a pipe bender.

Field Connection Pipe Size Detail

A table provides specific liquid and gas pipe sizes for various indoor and outdoor unit models, along with the refrigerant type (R410A or R22). For FD130DSV16/FD120GRV16 and R130DSY16/R120GRY16, a reducer is needed at the indoor unit end for gas pipe connection.

Precautions on Refrigerant Piping

Only the designated refrigerant should be used, and no other substances like air or nitrogen should mix into the cycle. Any refrigerant gas leaks during work require thorough room ventilation. The correct refrigerant type must be added as detailed in the table. Installation tools must be exclusively used for specific refrigerant types to withstand pressure and prevent foreign materials (e.g., mineral oils, moisture) from mixing into the system.

Special Precautions When Mounting TXV Bulb

The TXV bulb should be clamped to the suction line near the evaporator outlet, preferably on a horizontal run. The suction line must be completely clean before clamping the bulb. The bulb should be clamped to a free-draining suction line and insulated from ambient temperature. After installation, the TXV bulb must be fixed at the 8 o'clock or 4 o'clock position on the suction line.

Piping Works & Brazing Technique

Contaminated or damaged copper tubing should not be used. If any piping, evaporator, or condenser has been exposed to air for more than 15 seconds, it must be vacuumed and purged with field-supplied refrigerant. Plastic, rubber plugs, and brass nuts should remain on valves, fittings, tubings, and coils until ready for connection. During brazing, nitrogen gas must be passed through the coil and joints to prevent soot formation inside copper tubings. Pipes should be cut stage by stage with a pipe cutter, advancing the blade slowly to avoid distortion and burrs. Burrs must be removed from cut edges, holding the pipe end downwards to prevent metal chips from entering.

Piping Connection To The Units

The center of the piping should be aligned, and flare nuts tightened sufficiently by hand, then fully tightened with a torque wrench until it clicks. The tightening direction must follow the arrow indicated on the wrench. A table provides torque values for different pipe sizes.

Electrical Connection

Electrical connection values are for information only and must comply with local/national codes and regulations. The appropriate voltage range should be checked against the unit's data label. Specifications for power supply cable size, number of conductors, interconnection cable size, and recommended fuse amperage are provided for various indoor and outdoor unit models, including single-phase and three-phase systems. Wiring diagrams illustrate connections for different unit configurations.

Overall Checking

After installation, a thorough check is required:

  1. Ensure the unit is mounted solidly and rigidly.
  2. Verify that piping and connections are leak-proof after charging.
  3. Confirm proper wiring has been completed.
  4. Conduct a drainage check by pouring water into the left side of the drain pan (drainage is on the right side of the unit).
  5. Perform a test run after water drainage and gas leakage tests.
  6. Observe the unit: check if the electric plug is firmly inserted, if there are any abnormal sounds, and if water drainage is smooth.
  7. Verify that the condenser fan is running, blowing warm air off the condensing unit.
  8. Confirm that the evaporator blower is running and discharging cool air.
  9. Note that the remote controller incorporates a 3-minute delay before the outdoor condensing unit starts up.

Vacuuming and Charging

Vacuuming is essential to eliminate moisture and air from the system. The outdoor unit is equipped with valve fittings. Before vacuuming, a leak check of the refrigeration circuit must be performed. Flexible hoses should be connected to the charging nipples via standard servicing valves and pressure gauges. The system should be vacuumed to at least 500 microns Hg. The unit should not be started while vacuuming.

Before recharging, the vacuum must be held at 500 microns Hg for at least 15 minutes. Then, break the vacuum by charging the correct refrigerant type. The unit should operate for 15 minutes to ensure the refrigerant charge is correct. After confirming the charge, remove flexible hoses and replace caps.

Precautions While Charging

Refrigerant should only be charged after field work, leak testing, and vacuum drying are complete. The maximum permissible charge must not be exceeded to avoid liquid hammer. Charging with unstable substances can cause explosions and accidents, so only appropriate refrigerant types should be used.

System Refrigerant Charge Level Guidelines

A table provides refrigerant charge levels (kg/7.5m pipe length) for various indoor and outdoor unit models in cooling-only operation. Specific notes are included for multi-unit systems, detailing additional charge requirements for standard pipe lengths. A minimum pipe length of 7.5m must be maintained during installation.

Additional Charge

A table specifies additional refrigerant charge (kg/meter) based on liquid pipe size. This is a guideline for longer piping applications, and actual charge may vary based on application and site conditions.

Oil Refill Charge Guidelines

In case of a major oil spill or loss due to leakage, all remaining oil must be removed from the compressor, and fresh oil charged according to the provided table. To remove oil, the compressor should be removed from the system, tilted to allow all oil to drain from the suction port. The quality of the oil (clear, not black or turbid) determines if the same oil can be used for refilling or if fresh oil is required. Oil should be charged through the suction port of the compressor.

Special Precautions When Charging Unit With Scroll Compressors

These precautions apply to Scroll compressors using R22, R407C, R134A, R404A, R507, and R410A refrigerants. Scroll compressors have high volumetric efficiency and can quickly pump a deep vacuum if refrigerant is insufficient or added too slowly. Low suction pressure can lead to high discharge temperatures, causing poor lubrication and high friction between scroll flanks and tips, generating excessive heat. This can damage the Scroll spirals and orbiting Scroll bearing, potentially leading to failure within minutes or hours. Other charging problems like undercharging, overcharging, moisture, or air in the system can also cause compressor failure.

Minimal equipment is needed for field charging: service gauges, hoses, vacuum pump, vacuum gauge, scales, and thermometer. The proper refrigerant charge must follow manufacturer recommendations.

For single-phase compressors, the system should be evacuated to 500 microns Hg (67Pa) using short, large-diameter hoses connected to unrestricted service ports. A reliable vacuum gauge is essential. Liquid refrigerant should be charged through the liquid line charging port until flow stops or the correct charge is weighed in. If additional charge is needed, start the system and slowly bleed liquid into the suction side, carefully monitoring suction and discharge pressures to ensure suction pressure does not fall below 25 psig (1.7 bar). Various methods for controlled liquid charging into the suction side are listed.

For three-phase compressors, the procedure is similar, but if the compressor runs in the wrong direction on starting, any two phases must be reversed. Short-term reverse rotation will not damage the compressor. Scroll compressors have internal discharge temperature protectors that trip and lock out the compressor for 30 minutes if discharge temperatures become dangerously high. The module can be reset by breaking the power supply to the control circuit after the compressor cools down. Bypassing this protector can damage the compressor and lead to premature failure.

Caution is advised regarding refrigerant leaks: air conditioning facilities must be installed in a sufficiently large room to ensure that the maximum concentration level of refrigerant gas is not exceeded in the event of a major leak, in accordance with local regulations and standards.

Standard Operating Conditions

A graph illustrates the continuous operation range based on indoor and outdoor temperatures (CDB). Notes specify the conditions for the graph: equivalent piping length of 7.5m, level difference of 0m, and high airflow rate.

Auto Random Re-Start Function

If a power cut occurs during operation, the unit will automatically resume the same operating mode when power is restored (applicable only to units with this feature).

Service and Maintenance

Maintenance procedures are outlined for indoor air filters and the indoor unit.

  • Indoor air filter: Dust should be removed with a vacuum cleaner or by washing in lukewarm water (below 40°C) with a neutral cleaning detergent. The filter should be rinsed well, dried, and then replaced. Gasoline, volatile substances, or chemicals should not be used for cleaning. This should be done at least once every 2 weeks, or more frequently if necessary.
  • Indoor unit: Dirt or dust on the grille or panel should be cleaned by wiping with a soft cloth soaked in lukewarm water (below 40°C) and a neutral detergent solution. Gasoline, volatile substances, or chemicals should not be used for cleaning the indoor unit. This should be done at least once every 2 weeks, or more frequently if necessary.

Troubleshooting

A troubleshooting guide lists common fault conditions, their causes, and recommended actions.

  • Compressor not starting after 3 minutes: Protection against frequent starting; wait 3-4 minutes.
  • Unit not operating: Power failure, blown fuse, disconnected power plug, or incorrect delay timer setting. If the fault persists, contact the installer.
  • Low airflow: Dirty air filter, open doors/windows, clogged air suction/discharge, or regulated temperature not high enough.
  • Bad discharge air odor: Caused by cigarettes, smoke particles, perfume adhering to the coil.
  • Condensation on front air grille: High air humidity after extended operation.
  • Water flowing from unit: Set temperature too low; increase temperature and operate at high fan speed.
  • Hissing airflow sound: Switch off unit and call dealer.
  • Refrigerant fluid flowing into evaporator coil: Normal operation.
  • Room Temperature Sensor Fail (rS F): Sensor is short/open/not connected; resets automatically when sensor is corrected.
  • Indoor Antifreeze sensor Fail (CSF1): Sensor is short/open/not connected; resets automatically when sensor is corrected.
  • HP Error (HP1): Very high discharge pressure, condenser fan not working, or very high ambient temperature. Auto-resets, but 3 errors within 40 minutes lead to manual reset mode.
  • LP Error (LP1): Very low suction pressure. Auto-resets, but 3 errors within 40 minutes lead to manual reset mode.
  • SPPR Error (SPPR): Phase absence, reverse, unbalance, under/over voltage. Auto-resets when corrected.
  • Airflow Error (AF): IDU fan faulty (current < 0.5 amp). Auto-resets after 5 minutes, but 3 errors within 20 minutes lead to manual reset mode.
  • Communication Failure (C-Er): Communication wire break or faulty. Resets after changing communication wire.
  • Indoor Antifreeze Activation (df1): Indoor coil tube temperature ≤ 1°C. Check unit airflow for restrictions (air filter block) or low gas charge/refrigerant circuit partial blockage.

If any fault persists, the local dealer/serviceman should be contacted.

Phase Protector

Units with Scroll Compressors can only rotate in one direction. A phase protector prevents incorrect wiring of electrical phases. If phases are not connected correctly, the protector activates, and the unit will not start. This device is located in the outdoor unit's control box. A table shows LED indicator lights (LED, RV, UV, OV, AS) for normal operation and various fault conditions (single phasing, phase reversal, unbalance, over voltage, under voltage), along with recommended actions (switch off unit, check wiring/voltage).

SLM Controller Indication

A diagram illustrates the SLM controller with numbered indications for various functions:

  1. Program/Day indicators (PROG, MO, TU, WE, TH, FR, SA, SU, DAILY)
  2. Mode button
  3. Fan Speed button
  4. Menu button
  5. Reset/Cancel button
  6. Up/Down arrow buttons (6.1 for Down, 7.1 for Up)
  7. Filter Reset indicator
  8. Timer button
  9. Energy Saver button
  10. On/Off switch
  11. IR Sensor (for wireless remote)

Operating Instruction

  • Temperature (LCD Display): Use UP/DOWN keys to increase or decrease the set temperature (range 16°C to 32°C).
  • Mode: Displays selected operating mode (Cool Mode/Fan Mode).
  • Fan: Displays selected ventilation speed (LOW/MED/HIGH). Automatic speed selection adjusts to room temperature in cool mode (not available in FDR200FRY16).
  • Menu Mode: Pressing "MENU" activates menu options: Key Pad Lock, Clock Setting, Filter Reset, Factory Reset.
    • Key Pad Lock: Press MENU, then use UP/DOWN to toggle lock status. Locked keypad allows only ON/OFF, FAN SPEED, MODE & MENU keys to be active. Invalid key presses flash a symbol 3 times.
    • Clock Setting: Press MENU, navigate to CLOCK symbol, press Enter. Use LEFT/RIGHT to change day, then HOUR/MINUTE. Use UP/DOWN to adjust time. AM/PM changes with HOUR.
    • Filter Cleaning Reminder: "FILTER" symbol blinks after 200 hours of fan run. Navigate to FILTER symbol in Menu and press Enter to reset.
    • Factory Reset: Navigate to FAC SET symbol in Menu and press Enter. Resets settings to: Temp 24°C, Cool Mode, High Fan Speed, Filter Timer to Zero. Clears all 7-day programmable timers.
  • Reset/Cancel: Resets or cancels current operation.
  • Temperature Setting: UP/DOWN keys change timers and clock in setting modes, not set-temperature.
  • Right/Left: Moves cursor left or right to other options.
  • Timer: Pressing "TIMER" displays PROG MO TU WE TH FR SA SU and DAILY. PROG MO flashes to indicate Monday timers. Use LEFT/RIGHT to navigate days. One On-Timer and one Off-Timer per day, plus a "Daily" feature.
    • Setting Timers: Press Enter to set day. ON TIME flashes, use LEFT/RIGHT to switch between HOUR & MINUTES, UP/DOWN to adjust. OFF TIME is set similarly.
    • Daily Timer: If "Daily" is selected, the timer is effective every day.
  • Energy Saver: Activates/deactivates Energy Saver Mode (only in Cool mode). Sets temperature to 26°C and fan speed to MEDIUM.
  • On/Off Switch: Press once to start, again to stop.
  • IR Sensor: For wireless remote functions (refer to wireless remote manual).

Daikin FDR200FRY16 Specifications

General IconGeneral
BrandDaikin
ModelFDR200FRY16
CategoryAir Conditioner
LanguageEnglish

Related product manuals