REMOVAL
PROCEDURE
SERVICE MANUAL
Indoor Unit
Inverter / Non-Inverter
Wall Mounted Type
5.0/6.0/7.1 kW Class
15000/18000/24000 Btu/h Class
Si041142
Question and Answer IconNeed help?

Do you have a question about the Daikin FT50HV1 and is the answer not in the manual?

Daikin FT50HV1 Specifications

General IconGeneral
BrandDaikin
ModelFT50HV1
CategoryAir Conditioner
LanguageEnglish

Summary

Daikin Indoor Unit Removal of Air Filters and Front Panel

Remove Air Filters

Push up the center knob of the air filter, unfasten hooks, and pull filter downward.

Remove Titanium Apatite Filters

Push up the filter bottom, unfasten hooks, and remove the filter.

Remove Front Panel

Open front panel further, release shafts, and remove the panel.

Daikin Indoor Unit Removal of Front Grille

Remove Service Cover

Remove the screw and detach the service cover.

Remove Front Grille

Remove 3 screws, unfasten 3 top hooks, and pull grille out.

Daikin Indoor Unit Removal of Horizontal and Vertical Blades

Remove Horizontal Blades

Open blades, bend slightly to release center shaft, release left shaft, slide to release right shaft.

Remove Vertical Blades

Release right and left shafts, unfasten 3 hooks per set, pull blades rightward.

Daikin Indoor Unit Removal of Electrical Box, PCBs, and Swing Motors

Remove Electrical Box

Remove drip proof plate, cut clamp, pull thermistor, remove earth wire, disconnect connections, remove terminal board, disconnect motor connectors, remove box.

Remove PCBs

Remove screw, unfasten shield plate hook, press signal receiver unit, cut clamp, remove PCBs and connectors.

Remove Horizontal Swing Motor

Remove screw, then remove the swing motor.

Remove Vertical Swing Motor

Remove swing shaft, detach motor assembly, then remove the motor.

Daikin Indoor Unit Removal of Indoor Heat Exchanger

Disconnect Refrigerant Piping

Hold unit, pull drain hose, unscrew flare nuts for gas and liquid piping.

Remove Indoor Unit

Detach the indoor unit from the installation plate.

Remove Indoor Heat Exchanger

Unfasten hooks on left and right sides, pull exchanger forward, unfasten hooks, and lift.

Daikin Indoor Unit Removal of Fan Motor and Fan Rotor

Remove Right Side Plate

Remove 2 screws, lift and remove the right side plate.

Remove Fan Motor and Rotor

Remove fixing plate screw, remove fan rotor screw, remove fan motor, remove fan rotor, remove side plates, remove bearing.