EDUS041502 Electric Characteristics
Split Type Air Conditioners FTK(X)-N Series 53
10.Electric Characteristics
3D093165
Unit Combination Power Supply Compressor OFM IFM
Indoor Unit Outdoor Unit Hz - Volts Voltage Range MCA MFA RHz RLA W FLA W FLA
FTK09NMVJU RK09NMVJU
60 - 208
Min. 187 V
Max. 253 V
12.1 15 64 6.8 14 0.13 21 0.20
60 - 230
FTK12NMVJU RK12NMVJU
60 - 208
Min. 187 V
Max. 253 V
12.2 15 88 7.5 18 0.15 28 0.23
60 - 230
FTK18NMVJU RK18NMVJU
60 - 208
Min. 187 V
Max. 253 V
18.3 20 70 10.0 69 0.45 46 0.30
60 - 230
FTK24NMVJU RK24NMVJU
60 - 208
Min. 187 V
Max. 253 V
18.3 20 92 12.0 58 0.38 46 0.30
60 - 230
FTX09NMVJU RX09NMVJU
60 - 208
Min. 187 V
Max. 253 V
12.1 15 88 8.5 14 0.13 21 0.20
60 - 230
FTX12NMVJU RX12NMVJU
60 - 208
Min. 187 V
Max. 253 V
12.2 15 96 8.5 18 0.15 28 0.23
60 - 230
FTX18NMVJU RX18NMVJU
60 - 208
Min. 187 V
Max. 253 V
18.3 20 90 10.8 69 0.45 46 0.30
60 - 230
FTX24NMVJU RX24NMVJU
60 - 208
Min. 187 V
Max. 253 V
18.3 20 96 12.0 58 0.38 46 0.30
60 - 230
Symbols: Notes:
MCA : Min. circuit amps (A) 1. RHz is the max frequency that comes in cooling operation and
heating operation.
2. RLA is the max current that comes in cooling operation and heating
operation.
3. Maximum allowable voltage variation between phases is 2%.
4. Select wire size based on the larger value of MCA.
5. Instead of a fuse, use a circuit breaker.
6. Be sure to install a ground leak detector.
(This unit uses an inverter, which means that a ground leak detector
capable of handling high harmonics must be used in order to prevent
malfunctioning of the ground leak detector.)
MFA : Max. fuse amps (A)
RHz : Rated operating frequency (Hz)
RLA : Rated load amps (A)
OFM : Outdoor fan motor
IFM : Indoor fan motor
W : Fan motor rated output (W)
FLA : Full load amps (A)