EasyManua.ls Logo

Daikin FTK35JVE9 - 3.40 Protection Control of SkyAir Indoor Units

Daikin FTK35JVE9
410 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
System control Si18-201
156 Main Functions
The motorized valve operating amount is determined based on deviation EGA between each
room unit's gas pipe temperature and of DGAV after GFTUYU correction and previous deviation
EGAZ.
(Example) The following example is based on room A.
EGA = DGA - DGAV
When the operating flow rate of EVA is QRGA
QRGA = KPCB (0.05) × ((EGA-EGAZ) + KIB (0.32) × (EGA + EGAZ))
= 0.05 × (EGA - EGAZ) + 0.016 × (EGA + EGAZ)
When QRGA
QHENC(-0.12), the following condition is set: QRGA
QHENC (-0.12 Nm³/
hr).
Outside Air Temperature Gas Pipe Lower-Limit Temperature
-5 0
01
52
10 3
15 4
20 5
25 6
30 7
35 8
40 9
45 10

Table of Contents

Related product manuals