EasyManuals Logo

Daikin FTKD50BVMT User Manual

Daikin FTKD50BVMT
210 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #127 background imageLoading...
Page #127 background image
Troubleshooting Si04-306
118 Service Diagnosis
4.18 Output Over Current Detection
Remote
Controller
Display
L5
Method of
Malfunction
Detection
An output over-current is detected by checking the current that flows in the inverter DC section.
Malfunction
Decision
Conditions
A position signal error occurs while the compressor is running.
A speed error occurs while the compressor is running.
An output over-current input is fed from the output over-current detection circuit to the
microcomputer.
The system will be shut down if the error occurs 16 times.
Clearing condition: Continuous run for about 5 minutes (normal)
Supposed
Causes
Over-current due to defective power transistor
Over-current due to wrong internal wiring
Over-current due to abnormal supply voltage
Over-current due to defective PCB
Error detection due to defective PCB
Over-current due to closed stop valve
Over-current due to compressor failure
Over-current due to poor installation condition

Table of Contents

Other manuals for Daikin FTKD50BVMT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FTKD50BVMT and is the answer not in the manual?

Daikin FTKD50BVMT Specifications

General IconGeneral
BrandDaikin
ModelFTKD50BVMT
CategoryAir Conditioner
LanguageEnglish

Related product manuals