Si04-306 Others
Others 181
1.2 Jumper Settings
1.2.1 When Two Units are Installed in One Room
When two indoor units are installed in one room, the two wireless remote controllers can be set
for different addresses.
How to set the different addresses
Control PCB of the indoor unit
(1) Remove the front grille. (3 screws)
(2) Remove the electrical box (1-screw).
(3) Remove the drip proof plate. (4 tabs)
(4) Cut the address jumper JA on the control PCB.
Wireless remote controller
(1) Slide the front cover and take it off.
(2) Cut the address jumper J4.
1.2.2 Jumper Setting
(R2871) (R2872)
Jumper
(On indoor control PCB)
Function When connected
(factory set)
When cut
JC Power failure
recovery function
Auto start Unit does not resume operation
after recovering from a power
failure. Timer ON-OFF settings
are cleared.
JB Fan speed setting
when compressor is
OFF on thermostat.
Fan speed setting ;
Remote controller
setting
Fan rpm is set to 0
<Fan stop>

Table of Contents

Other manuals for Daikin FTKD50BVMT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FTKD50BVMT and is the answer not in the manual?

Daikin FTKD50BVMT Specifications

General IconGeneral
BrandDaikin
ModelFTKD50BVMT
CategoryAir Conditioner
LanguageEnglish

Related product manuals