EasyManua.ls Logo

Daikin FTXA20AW - Operation Starts and the Unit Stops Immediately; Operation Stops, Unit Cannot Start for a While

Daikin FTXA20AW
192 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1 | Troubleshooting
Service manual
38
FTXA20~50A(W)(S)(T) + FTXA20~50B(B)(S)(T) + RXA42+50A +
RXA20~35A(9) + RXA42+50B
Split Stylish R32
ESIE18-03D – 2021.05
1.6.8 Operation starts and the unit stops immediately
Check Detail
Check the power supply. Is the capacity of the safety breaker as
specified?
If the earth leakage breaker is too
sensitive, then increase the set value
of the earth leakage current of the
breaker or replace the breaker.
Is the circuit exclusive?
Is the rated voltage (± 10%) supplied?
Is there an incorrect size of
connection wiring?
Check the refrigerant charge. Overcharge.
Air in the system.
Water in the system.
Check the fan motor. Check the magnetic switch.
Check the overcurrent relay.
Check the four way valve coil. Is there a short circuit?
Is the four way valve coil broken?
Check the outdoor PCB. Is there a short circuit?
Is the outdoor PCB broken?
Check the heat exchanger. Soiled heat exchanger, obstruction.
Check the airflow. Soiled air filter, obstruction, installation
space.
1.6.9 Operation stops, unit cannot start for a while
Check Detail
Check if standby function is activated. Compressor delay timer is counting.
Wait for minimum 3 minutes.
Check the power supply. Low voltage?
Is the size of the power cable
sufficient?
Check the refrigerant charge. Incorrect charge.
Air in the system.
Water in the system.
Obstruction in the system.
Check compressor. Overcurrent relay.
Protection thermostat.

Table of Contents

Related product manuals