Capacity Tables EDUS041129
14 Split Type Air Conditioners FTXS-L Series
FTXS36LVJU + RKS36LVJU (60 Hz, 208 - 230 V)
3D071131A
AFR 21.8
BF 0.27
Temp: Celsius
TC, SHC, PI: kW
INDOOR OUTDOOR TEMPERATURE (°CDB)
EWB EDB 20 25 30 32 35 40
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 7.15 5.14 1.54 7.15 5.14 1.77 7.15 5.14 2.05 7.15 5.14 2.17 7.15 5.14 2.38 7.15 5.14 2.67
16.0 22.0 8.92 5.78 2.09 8.92 5.78 2.44 8.92 5.78 2.87 8.92 5.78 3.07 8.92 5.78 3.41 8.92 5.78 3.89
18.0 25.0 10.82 6.74 2.80 10.82 6.74 3.35 10.75 6.70 3.97 10.55 6.60 4.10 10.26 6.45 4.29 9.60 6.12 4.24
19.4 26.7 11.82 7.38 3.25 11.48 7.20 3.66 10.99 6.95 3.98 10.79 6.86 4.11
10.50 6.71 4.30 9.82 6.38 4.24
22.0 30.0 12.69 7.14 3.37 12.20 6.91 3.69 11.71 6.69 4.01 11.52 6.60 4.14 11.23 6.47 4.33 10.50 6.16 4.24
24.0 32.0 13.18 6.90 3.39 12.69 6.69 3.71 12.20 6.49 4.03 12.00 6.41 4.16 11.71 6.29 4.35 10.95 5.99 4.24
Temp: Fahrenheit
TC, SHC: kBtu/h
PI: kW
INDOOR OUTDOOR TEMPERATURE (°FDB)
EWB EDB 68 77 86 90 95 104
°F °F TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
57.2 68.0 24.39 17.54 1.54 24.39 17.54 1.77 24.39 17.54 2.05 24.39 17.54 2.17 24.39 17.54 2.38 24.39 17.54 2.67
60.8 71.6 30.43 19.72 2.09 30.43 19.72 2.44 30.43 19.72 2.87 30.43 19.72 3.07 30.43 19.72 3.41 30.43 19.72 3.89
64.4 77.0 36.91 23.00 2.80 36.91 23.00 3.35 36.67 22.87 3.97 36.00 22.52 4.10 35.00 22.01 4.29 32.75 20.89 4.24
67.0 80.0 40.33 25.18 3.25 39.16 24.57 3.66 37.49 23.72 3.98 36.83 23.39 4.11
36.00 22.89 4.30 33.52 21.78 4.24
71.6 86.0 43.31 24.36 3.37 41.64 23.58 3.69 39.97 22.83 4.01 39.30 22.53 4.14 38.30 22.09 4.33 35.82 21.01 4.24
75.2 89.6 44.96 23.54 3.39 43.29 22.83 3.71 41.62 22.14 4.03 40.95 21.86 4.16 39.95 21.46 4.35 37.35 20.43 4.24
Symbols: Note:
AFR : Airflow rate (m
3
/min.) 1. Ratings shown are net capacities which include a deduction for indoor fan
motor heat.
2. shows nominal (rated) capacities and power input.
3. TC, PI and SHC must be calculated by interpolation using the figures in
the tables. (Figures out of the tables should not be used for calculation.)
4. SHC values not included in the table must be calculated using
interpolation with values of direct proportion.
5. Capacities are based on the following conditions.
Corresponding refrigerant piping length : 25 ft
Level difference : 0 ft
6. Cooling capacity at –15°CDB and 5°FDB.
BF : Bypass factor
EWB : Entering wet bulb temp. (°C) / (°F)
EDB : Entering dry bulb temp. (°C) / (°F)
TC : Total capacity (kW) / (kBtu/h)
SHC : Sensible heat capacity (kW) / (kBtu/h)
PI : Power input (kW)
Temp: Celsius
TC, SHC, PI: kW
60 Hz, 208 - 230 V
INDOOR OUTDOOR
EWB EDB –15 (°CDB)
°C °C TC SHC PI
14.0 20.0 5.67 4.42 0.54
Temp: Fahrenheit
TC, SHC: kBtu/h
PI: kW
60 Hz, 208 - 230 V
INDOOR OUTDOOR
EWB EDB 5 (°FDB)
°F °F TC SHC PI
57.2 68.0 19.35 15.08 0.54