SiBE01-829 Troubleshooting
Service Diagnosis 51
Troubleshooting
Check No.06
Refer to P.55
Check No.07
Refer to P.56
Check No.09
Refer to P.57
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Open the stop valve.
Check the stop valve.
YES
NO
Is it opened?
(R8506)
Replace the fan motor.
Repair the connector or fan
motor lead wires.
Replace the heat exchanger
thermistor.
Replace PCB.
Correct the connection.
Change the air outlet grille
position.
Clean the heat exchanger.
Change the installation
location.
Check the installation space.
Check the connector connection.
Abnormal
Normal
YES
Normal
Normal
Abnormal
NO
Abnormal
Is it normal?
Judgment
Check No. 09
Check the outdoor fan.
Check No. 07
Check the installation
condition.
Check No. 06
Check the heat exchanger
thermistor.