4
ELECTRICAL WIRING CONNECTION
This is proposed wiring connection. It may change subject to the chiller unit and must comply with the local and national code and regulations.
N
FCU 1 FCU 2
x1
x2
x3
R
S
T
N
220~240V/1 /50Hz
X1,X2,X3
VA LV E
L
FCU 3
N
VA LV E
L
N
VA LV E
L
3WV
3WV
3WV
3WV
3 way valve
Relay (220-240V,10A)
Chiller
Model: FWC07AATNMV1 / FWC08AATNMV1 / FWC10AATNMV1 / FWC11AATNMV1 / FWC12AATNMV1
Model: FWC07AATNMV1 / FWC08AATNMV1 / FWC10AATNMV1 / FWC11AATNMV1 / FWC12AATNMV1
Model
FWC07AATNMV1 FWC08AATMNV1 FWC10AATNMV1 FWC11AATNMV1 FWC12AATNMV1
Voltage range** 220V-240V/1Ph/50Hz +
!
Recommended fuse* A 2 2 222
Power supply cable size* mm
2
1.5 1.5 1.5 1.5 1.5
Number of conductors 3 3 333
Note : Unit comes in standard heatpump and for valve application.
IMPORTANT: * These values are for information only. They should be checked and selected to comply with local and/or
national codes and regulations. They are also subject to the type of installation and size of conductors.
** The appropriate voltage range should be checked with label data on the unit. A main switch or other means
for disconnection, having a contact separation in all poles, must be incorporated in the fixed wiring in
accordance with relevant local and national legislation.
•
All wires must be firmly connected.
•
All wires must not touch the water piping, or any moving parts of the fan motor.
•
The power supply cord must be equivalent to H05VV-F (60227 IEC 52 or 60227 IEC 53) which is the minimum
requirement, and to be used in protective tube.
PART NUMBER: 08024 091939
CAUTION !
VA LV E L N
THERMIISTOR
LCD WIRELESS
CONTROLLER
WIRED
CONTROLLER
COIL SENSOR
BLACK
WHITE
RED
FAN MOTOR
BROWN (FL)
ORANGE (FM)
A.C L.C
M.C
PURPLE (FH)
RED
PURPLE
AIR SWING
MOTOR
LED/IR RECEIVER
BLACK
BLUE
BLUE
RED
BLACK
DRAIN
PUMP
LEVEL SWITCH
GREEN/YELLOW
GREEN/YELLOW
GREEN/YELLOW
RED
(PRINTED CIRCUIT BOARD)
GREEN/YELLOW
TO 3 WAY
VALVE
E
N
L
220~240V
1 PHASE 50Hz
IR.RCV
10
9
16
FIELD SUPPLY WIRING
WITH JUMPER FOR HEAT PUMP
WITHOUT JUMPER FOR COOLING
WITH JUMPER FOR VALVE APPLICATION
WITHOUT JUMPER FOR VALVELESS APPLICATION