SiBE611027_A Specifications
Specifications 4
1. Specifications
Note:
1. The range of usable water temperature is 6°C (min.) to 60°C (max.).
2. Maximum allowable water pressure is 1.18 MPa.
3. Comply with drinking water directive 98/83/EC for chilled water, hot water and make-up water.
4. The amount of water circulation should be 3 L/min to 15 L/min. (0.18 m³/h to 0.9 m³/h).
5. Allowable model of hydrobox interlinking is BA-series or later. (Refer to page 80 for detail.)
6.
The data are based on the following conditions.
50 Hz, 220 - 230 - 240 V / 60 Hz, 220 V
Model
FWXV15AVEB FWXV20AVEB
Cooling Heating Cooling Heating
Dimensions (H × W × D) mm 600 × 700 × 210 600 × 700 × 210
Packaged Dimensions (H × W × D) mm 696 × 786 × 280 696 × 786 × 280
Weight kg 15 15
Gross Weight kg 19 19
Front Panel Color White White
Fan
Type Turbo Fan Turbo Fan
Speed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto
Airflow Rate
m³/h
(cfm)
H 318 (188) 318 (188) 474 (280) 474 (280)
M 228 (135) 228 (135) 354 (209) 354 (209)
L 150 (89) 150 (89) 240 (142) 240 (142)
SL 126 (74) 126 (74) 198 (117) 198 (117)
Capacity
Total Capacity
(Rated: M)
kW 1.2 1.5 1.7 2.0
Btu/h 4,100 5,100 5,800 6,800
Sensible Capacity
(Rated: M)
kW 0.98 1.4
Btu/h 3,300 4,800
Water Volume
(Rated: M)
m³/h 0.20 0.26 0.29 0.34
L/min 3.4 4.3 4.9 5.7
Water Pressure Drop
(Rated: M)
kPa10131922
Running Current (Rated: M) A 0.08 0.08 0.10 0.10
Power Consumption (Rated: M) W 13 13 15 15
Power Factor (Rated: M) % 70.7 70.7 65.2 65.2
Operation
Sound
(Rated: M) dB(A) 19 19 29 29
Sound Power (Rated: M) dB(A) 35 35 45 45
Air Direction Control Right, Left, Horizontal, Downward Right, Left, Horizontal, Downward
Air Filter Removable / Washable / Mildew Proof Removable / Washable / Mildew Proof
Temperature Control Microcomputer Control Microcomputer Control
Connection
Pipe Size
Inlet inch G 1/2 G 1/2
Outlet inch G 1/2 G 1/2
Drain mm
φ
18
φ
18
Heat Insulation Both Inlet and Outlet Pipes Both Inlet and Outlet Pipes
Drawing No. 3D066678A
Conversion Formulae
Btu/h = kW × 3412
cfm = m³/min × 35.3
Cooling Heating
Room Temperature: 27°CDB, 19°CWB
Entering Water Temperature: 7°C
Water Temperature Rise: 5 K
Room Temperature: 20°CDB
Entering Water Temperature: 45°C
Water Temperature Drop: 5 K