SiBE611027_A Indoor Unit
Removal Procedure 72
1.9 Removal of Fan Rotor / Fan Motor
Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Step Procedure Points
1. Remove the fan rotor.
The screw has reverse
winding.
Nut size: M6
When reassembling, align
mark of the indoor fan
with D-cut section of the
motor shaft.
1
Remove the 4 screws
and remove the
bellmouth.
2 Remove the nut and
remove the fan rotor.
2. Remove the fan motor.
1 Release the harness of
the fan motor from the
hook.
Bellmouth
(R12503)
10 mm
(R12236)
Nut
Fan rotor
(R12504)
Hook
(R12443)