Auxiliary Heater Setting EDUS391777-F17
52 FXSQ-TAVJU
14.Auxiliary Heater Setting
Auxiliary Electric Heater ON/OFF Temperature
Note: *1. S value varies automatically based on the room temperature trend.
: Factory setting
There is a limitation of combination between Ton and Toff as below due to 2°C (3.6°F) hysteresis required for reliability.
z: Available
—: Not available
Mode No. First Code No. Symbol
Second Code No.
01 02 03 04 05 06
11 (21)
1Ton
–4°C
(–7.2°F)
–3.5°C
(–6.3°F)
–3°C
(–5.4°F)
–2.5°C
(–4.5°F)
–2°C
(–3.6°F)
–1.5°C
(–2.7°F)
2Toff
–2°C
(–3.6°F)
–1.5°C
(–2.7°F)
–1°C
(–1.8°F)
–0.5°C
(–0.9°F)
0°C
(0°F)
0.5°C
(0.9°F)
Set temperature
Toff + S (*1)
Ton + S (*1)
Thermostat
OFF
Thermostat
ON
Second Code No.
Ton
01 02 03 04 05 06
–4°C
(–7.2°F)
–3.5°C
(–6.3°F)
–3°C
(–5.4°F)
–2.5°C
(–4.5°F)
–2°C
(–3.6°F)
–1.5°C
(–2.7°F)
Toff
06 0.5°C (0.9°F) zzzzzz
05 0°C (0°F) zzzzz
04 –0.5°C (–0.9°F) zzzz——
03 –1°C (–1.8°F) zzz———
02 –1.5°C (–2.7°F) zz————
01 –2°C (–3.6°F) z —————