EDUS391777-F17 Installation Manual
FXSQ-TAVJU 12
3P184443-13Z
12
English
(2) #HVGTRKRKPIKUƂPKUJGFEJGEMKHVJGFTCKPƃQYU
smoothly.
=9JGPVJGGNGEVTKEYKTKPIYQTMKUƂPKUJGF?
r Gradually pour 1/4 gal. (1
) of water from the inspec-
tion hatch at the bottom of the drain socket on the
left side of the drain socket into the drain pan giving
caution to avoid splashing water on the electric com-
RQPGPVUUWEJCUFTCKPRWORCPFEQPƂTOFTCKPCIGD[
operating the indoor unit under cooling mode accord-
ing to 10. FIELD SETTING. (Refer to Fig. 18)
Control box
Drain socket
Filling port
Drain pan
Drain socket
(with rubber cap)
Plastic container
for pouring water
Drain pump
position
Terminal block
for wiring between
the indoor and
outdoor units
Control box lid
Air outlet
Inspection
window
Screw
[Method of adding water]
Fig. 18
=9JGPVJGGNGEVTKEYKTKPIYQTMKUPQVƂPKUJGF?
r The electric wiring works (including grounding) must
DGECTTKGFQWVD[CSWCNKƂGFGNGEVTKEKCP
r +HCSWCNKƂGFRGTUQPKUPQVRTGUGPVCHVGTVJGGNGEVTKE
YKTKPIYQTMKUƂPKUJGFEJGEMVJGFTCKPCIGCEEQTFKPI
VQVJGOGVJQFURGEKƂGFKP[When the electric wiring
YQTMKUƂPKUJGF?.
1. 1RGPVJGEQPVTQNDQZNKFCPFEQPPGEVVJGUKPING
phase 208/230 V power supply to the terminal (L1,
L2) on the terminal block (X1M).
Connect the ground wiring to the ground terminal.
2. /CMGUWTGVJGEQPVTQNDQZNKFKUENQUGFDGHQTGVWTP-
ing on the power supply.
r Throughout the whole process, carry out the
work giving caution to the wiring around the con-
VTQNDQZUQVJCVVJGEQPPGEVQTUOC[PQVEQOGQHH
3. Gradually pour 1/4 gal. (1
) of water from the air out-
let on the left side of the drain socket into the drain
pan giving caution to avoid splashing water on the
electric components such as drain pump.
(Refer to Fig. 18)
4. When the power supply is turned on, the drain pump
will operate. Drainage can be checked at the trans-
parent part of the drain socket.
(The drain pump will automatically stop after 10
minutes.)
6JGFTCKPCIGQHYCVGTECPDGEQPƂTOGFYKVJYCVGT
level change in the drain pan through the access
window.
r Do not connect the drain piping directly to the
sewage that gives off ammonia odor.
The ammonia in the sewage may go through the
FTCKPRKRKPICPFEQTTQFGVJGJGCVGZEJCPIGTQH
the indoor unit.
r &QPQVCRRN[GZVGTPCNHQTEGVQVJGƃQCVUYKVEJ+V
may result in malfunction)
r Do not touch the drain pump.
Touching the drain pump may cause electric
shocks.
5. Turn off the power supply after checking drainage,
and remove the power supply wiring.
6. #VVCEJVJGEQPVTQNDQZNKFCUDGHQTG
(3) Sweating may occur and result in water leakage.
Therefore, make sure to insulate the following 2
locations (drain piping that laid indoors and drain
sockets).
r Use the provided sealing material (Large) (6), and
perform the thermal insulation of the metal clamp (1)
and drain hose (2) after checking the drainage of water.
(Refer to Fig. 19)
Start wrapping from where the
metal clamp (1) is tightened.
Wrap the sealing material (Large) (6)
so that the metal clamp (1) end side
may be doubled.
Metal clamp (1)
(accessory)
Drain hose (2)
(accessory)
Sealing material (Large) (6)
(accessory)
Sealing material - Large
(6) (accessory)
No clearance is
allowed.
Fig. 19