Specifications EDUS391777-F17
6 FXSQ-TAVJU
MSP Concealed Ducted Unit
Notes:
+ 1. Nominal cooling capacities are based on the following conditions:
Return air temperature: 80.0°FDB (26.7°CDB), 67.0°FWB (19.4°CWB)
Outdoor temperature: 95.0°FDB (35.0°CDB)
Equivalent refrigerant piping length: 25 ft (7.6 m) (Horizontal)
+ 2. Nominal heating capacities are based on the following conditions:
Return air temperature: 70.0°FDB (21.1°CDB).
Outdoor temperature: 47.0°FDB (8.3°CDB), 43.0°FWB (6.1°CWB)
Equivalent refrigerant piping length: 25 ft (7.6 m) (Horizontal)
+ 3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
+ 4. External static pressure is changeable in 13 stages (05~15 type), 11 stages (18~48 type), 10 stages (54 type)
within the ( ) range by remote controller.
+ 5. Air filter is not standard accessory, but please mount it in the duct system of the suction side.
Select its dust collection efficiency (gravity method) 50% or more.
+ 6. Anechoic chamber conversion value, measured under JIS conditions. During actual operation,
these values may be higher as a result of installation conditions.
7. Refer to Electric Characteristics for the power input.
Model FXSQ24TAVJU FXSQ30TAVJU
Power supply 1 phase, 60 Hz, 208/230 V 1 phase, 60 Hz, 208/230 V
+1 +3 Cooling capacity
Btu/h
(kW)
24,000 (7.0) 30,000 (8.8)
+2 +3 Heating capacity
Btu/h
(kW)
27,000 (7.9) 34,000 (10.0)
Casing / Color Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) in. (mm)
9-11/16 × 39-3/8 × 31-1/2
(245 × 1,000 × 800)
9-11/16 × 39-3/8 × 31-1/2
(245 × 1,000 × 800)
Coil (Cross
fin coil)
Rows×Stages×FPI 2×26×19 3×26×19
Face area ft² (m²) 3.10 (0.288) 3.10 (0.288)
Fan
Model — —
Type Sirocco fan Sirocco fan
Motor output W 230 230
Airflow rate (H/M/L)
cfm
(m³/min)
742/618/512
(21/17.5/14.5)
812/689/565
(23/19.5/16)
External static
pressure
in. H
2O
(Pa)
Standard 0.20 (0.60-0.20
+
4)
(50 (150-50))
Standard 0.20 (0.60-0.20
+
4)
(50 (150-50))
Drive Direct drive Direct drive
Temperature control
Microprocessor thermostat for cooling and
heating
Microprocessor thermostat for cooling and
heating
Sound absorbing thermal insulation material — +5— +5
Piping
connections
Liquid pipes in. (mm) φ3/8 (φ9.5) (Flare connection) φ3/8 (φ9.5) (Flare connection)
Gas pipes in. (mm) φ5/8 (φ15.9) (Flare connection) φ5/8 (φ15.9) (Flare connection)
Drain pipe in. (mm)
VP25
External dia. 1-1/4 (32)
Internal dia. 1 (25)
VP25
External dia. 1-1/4 (32)
Internal dia. 1 (25)
Weight lbs (kg) 77 (35) 82 (37)
+6 Sound pressure levels (H/M/L) dB(A) 36.0/32.0/29.0 37.5/34.0/30.0
+6 Sound power level dB(A) 64 65.5
Safety devices Fuse, Fan driver overload protector Fuse, Fan driver overload protector
Refrigerant control Electronic expansion valve Electronic expansion valve
Connectable outdoor unit R410A VRV series R410A VRV series
Standard accessories
Operation manual, Installation manual,
Drain hose, Sealing material, Clamps,
Washers, Screws, Insulation for fitting,
Clamp metal, Air discharge flange,
Air suction flange, Conduit mounting plate
Operation manual, Installation manual,
Drain hose, Sealing material, Clamps,
Washers, Screws, Insulation for fitting,
Clamp metal, Air discharge flange,
Air suction flange, Conduit mounting plate
Drawing No.
Specification C: 3D110282 C: 3D110282
Sound level C: 4D110416 C: 4D110417
() ()