5-5
NTC type USDA Sensor Characteristics, USDA1, USDA2, USDA3, CTS (Option)
Set sensor type "2" in 12 Configuration Set
in paragraph 2.3 for NTC type USDA sensor.
      
Temperature
(℃)
Temperature
(󱌞F
Resistance
kΩ)
Temperature
(℃)
Temperature
(󱌞F
Resistance
kΩ)
20 4 97.391 10 50 19.893
19 2 91.883 11 52 18.964
18 0 86.721 12 54 18.083
17 1 81.882 13 55 17.249
16 3 77.343 14 57 16.457
15 5 73.034 15 59 15.709
14 7 69.087 16 61 14.995
13 9 65.333 17 63 14.320
12 10 61.805 18 64 13.678
11 12 58.491 19 66 13.069
10 14 55.379 20 68 12.491
9 16 62.442 21 70 11.041
8 18 49.684 22 72 11.419
7 19 47.087 23 73 10.922
6 21 44.641 24 75 10.450
5 23 42.338 25 77 10.001
4 25 40.167 26 79 8.574
3 27 38.120 27 81 8.157
2 28 36.190 28 82 8.779
1 30 34.369 29 84 8.411
0 32 32.651 30 86 8.060
1 34 31.028 31 88 7.725
2 36 29.494 32 90 7.406
3 37 28.047 33 91 7.102
4 39 25.678 34 93 6.812
5 41 25.385 35 95 6.535
6 43 24.162 36 97 6.271
7 45 23.005 37 99 6.200
8 46 21.910 38 100 5.779
9 48 20.874 39 102 5.550
3P156427A
Receptacle for
NTC
setting "2"
0501-08LX10F11BEn.indd5-50501-08LX10F11BEn.indd5-5 2014/11/1916:41:492014/11/1916:41:49
https://daikin-p.ru

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin LX10F11B and is the answer not in the manual?

Daikin LX10F11B Specifications

General IconGeneral
BrandDaikin
ModelLX10F11B
CategoryInverter
LanguageEnglish

Related product manuals