2-39
029 Communication Interrupted
E903
Alarm
Logic
A communication error between CPU board and operation board
Possible
Causes
1. Open circuit between operation board (EC3) and CPU board (EC1)
2. Operation board failure
3. CPU board failure
Trouble
Shooting
Step 1. Check if the connector of cable between operation board EC3) and CPU board EC1)
is inserted securely.
Step 2. If there is no connection error between both boards, it seems to be operation board or
CPU board failure.
Replace in order starting from the CPU board.
Controller
Action
Communication InterruptedE903  Alarm display only
"Communication Interrupted" is displayed on LCD and E903 is recorded on trip report.)