Symptom Cause Checkpoint Remedy
Abnormal noise or vibration
Abnormal noise
Malfunction of
compressor
Auditory check Replace
Evaporator and
condenser fan
motors
Worn bearings
Fan blades
touching
Auditory check
Auditory and visual check
Repair as needed.
Abnormal vibration
Compressor
Fan motor
Loosen bolt
Auditory check
Visual check
Tighten bolts.
Piping
Removed or
loosen cramp
Auditory check
Visual check
Fix the cramp.
Abnormal frosting on compressor
Abnormal frosting
on compressor
and suction pipe
Condenser fan
stop
Defrost completed
Is condenser fan
stopped?
EIS, EOS
Is there no gap?
Inspection of EIS,EOS
Inspection of fan motor
Is there any frost
on the suction pipe?
Check the EEV.
Replace
Com
p
letion
Manual defrost
NO
YES
YES
NO
There is gap.
There is no gap.
YES
NO
Check of superheat
accuracy
Faulty operation
of electronic
expansion valve
(EEV)
2-52
0245-54LX10F11BEn.indd2-520245-54LX10F11BEn.indd2-52 2014/11/1916:37:012014/11/1916:37:01
https://daikin-p.ru

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin LX10F11B and is the answer not in the manual?

Daikin LX10F11B Specifications

General IconGeneral
BrandDaikin
ModelLX10F11B
CategoryInverter
LanguageEnglish

Related product manuals