EasyManuals Logo

Daikin MicroTech I Installation And Maintenance

Daikin MicroTech I
42 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #25 background imageLoading...
Page #25 background image

www.DaikinApplied.com 25 IM 1285-4 • MICROTECH III
Figure 28 continued: Code Update SIL
Page 3 of 9
4. Save the existing configuration and parameters to the memory card.
a. From the Main Menu select Service Menus then Save/Restore Settings.
b. Set SaveToCard option to Yes and press the Enter button. Wait till “Yes” reverts to “No”
5. Remove the SD card from the controller and inserting the SD card into the Laptop.
6. Verify 2 parameter files (Param.bin & Param.ucf) saved and their file sizes are larger than 100 KB
7. If the param file sizes are less than 100 KB then repeat step 4
8. If the files are not saving to the existing SD card then check the SD card lock or try a different SD card
9. This completes saving parameters to the SD card

Other manuals for Daikin MicroTech I

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin MicroTech I and is the answer not in the manual?

Daikin MicroTech I Specifications

General IconGeneral
BrandDaikin
ModelMicroTech I
CategoryController
LanguageEnglish

Related product manuals