One Event Schedule Menu
The One Event Schedule is used to set the start and stop times for one event.
Table 16: One Event Schedule Menu
Item Display Name Default Setting Range Password Level
Beg= MMMDD/99 @ HH:MM 00/00/00-12/31/99 @ 00:00 – 23:59 6
End= MMMDD/99 @ HH:MM 00/00/00-12/31/99 @ 00:00 – 23:59 6
Optimal Start Menu
The Optimal Start menu is used to set up the unit so it starts at the most efcient time before building occupancy.
Table 17: Optimal Start Menu
Item Display Name Default Setting Range Password Level
Enable= No No, Yes 6
Htg Rate= 0.4°F/min 0.0–1.0°F/min 2
Htg OAT= 35°F -40–60°F 2
Des Htg OAT= 0°F -40–60°F 2
Clg Rate= 0.4°F/min 0.0–1.0°F/min 2
Clg OAT= 85°F -60–140°F 2
Des Clg OAT= 95°F -60–140°F 2
Enable is an adjustable item that turns on the optimal start
feature. Setting the value to yes will activate this function.
Htg Rate is an adjustable item used by the controller in
determining the amount time before occupancy to start when
the Optimal Start parameter is set to “ON.”
Htg OAT is an adjustable item used by the controller in
determining the amount time before occupancy to start when
the Optimal Start parameter is set to “ON.”
Design Htg OAT is an adjustable item that sets the outdoor
air temperature at which the heating system could just hold the
load. The rate of temperature rise would equal zero.
Clg Rate is an adjustable item that sets the rate of temperature
drop in degrees per minute when the unit last started optimally
in cooling.
Clg OAT is an adjustable item that sets the outdoor air
temperature when the unit was last started optimally in cooling.
Design Clg OAT is an adjustable item that sets the outdoor
air temperature at which the cooling system could just hold the
load. Rate of temperature rise would equal zero.
Daylight Savings Menu
Table 18: Daylight Savings Menu
Item Display Name Default Setting Range Password Level
DLS Strt Mon= Mar
NA
Jan-Dec
2
DLS Strt Wk= 2ndWeek
1stSun
2ndSun
3rdSun
4thSun
5thSun
2
DLS End Mon= Nov
NA
Jan-Dec
2
DLS End Week= 1stWeek
1stSun
2ndSun
3rdSun
4thSun
5thSun
2
DLS Enable= Auto Off/Auto 2
DLS Strt Mon is an adjustable item that sets the month for
daylight savings time to begin.
DLS Strt Wk is an adjustable item that sets the week of the
month for daylight savings time to begin.
DLS End Mon is an adjustable item that sets the month for
daylight savings time to end.
DLS End Week is an adjustable item that sets the week of the
month for daylight savings time to end.
DLS Enable is an adjustable item that sets whether or not
daylight savings time is enabled.
OM 920-6 • MICROTECH UNIT CONTROLLER 32 www.DaikinApplied.com
Menu desCrIpTIons

Table of Contents

Other manuals for Daikin MicroTech I

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin MicroTech I and is the answer not in the manual?

Daikin MicroTech I Specifications

General IconGeneral
BrandDaikin
ModelMicroTech I
CategoryController
LanguageEnglish

Related product manuals