EasyManuals Logo

Daikin MicroTech I User Manual

Daikin MicroTech I
144 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #25 background imageLoading...
Page #25 background image
Occupancy
Menus in the Occupancy menu contain status and control
items that relate to unit occupied/unoccupied operation.
Table 3: Occupancy Menu
Item Display Name Default Setting Range Password Level
Occupancy=
Occ
Unocc
TntOvrd
6
Occ Mode= Auto/Net
Occ
Unocc
TntOvrd
Auto/Net
6
OccSrc= -
None
NetSchd
IntSchd
OneEvnt
RemoteSw
OccManCmd
OccMode
TStatTO
ManTO
6
UnoccSrc= -
UnoccDehum
UnoccClg
UnoccHtg
IntOptStrt
NetOptStrt
None
6
Tnt Ovrde Time= 0 0–300min 6
Occupancy is a status only item which indicates whether the
unit is currently in an occupied, unoccupied, or tenant override
mode of operation.
OccMode is an adjustable item which allows the unit to be
set for manual occupied or unoccupied operation, automatic
operation based on a time schedule input or manual tenant
override operation.
OccSrc is a status only item which indicates the input source
or function that is responsible for setting the Occupancy
parameter to “Occ” or “TntOvrd.”
UnoccSrc is a status only item which indicates the input
source or function that is responsible for running the unit while
the Occupancy parameter to “Unocc.”
Tnt Ovrd Time is an adjustable item which indicates the
amount of time remaining for unit operation since tenant
override operation was activated.
Menu desCrIpTIons
www.DaikinApplied.com 25 OM 920-6 • MICROTECH UNIT CONTROLLER

Table of Contents

Other manuals for Daikin MicroTech I

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin MicroTech I and is the answer not in the manual?

Daikin MicroTech I Specifications

General IconGeneral
BrandDaikin
ModelMicroTech I
CategoryController
LanguageEnglish

Related product manuals