4. Verify that the following are all selected from the screen
shown in Figure 58:
State setting = Online
Source of CP Values setting = Defaults and Include
NV type CPs

CPs
5. Click Next.
 .
6. Verify that Service pin is selected and then click Finish
(Figure 59).

7. The screen in Figure 60 appears.
8. Press the service pin button on the 
communication module. Refer to Figure 49 for the
location of the service button.

At this point, the application image starts loading the
 communication module. This process takes
approximately one minute (Figure 61).
The MTIII WSHP device changes color to green which
indicates successful commissioning (Figure 62).

 Communication Module –
Commissioned
In order to program another  device, it is necessary

three steps:
1. Right click on the commissioned  device
2. Select Commissioning
3. Left click on Decommission