ED 15103-6 • MICROTECH III WSHP UNIT CONTROLLER 30 www.DaikinApplied.com
ComprehensIve daTa Tables
Table 16: Network Variable Outputs (NVOs) - Ennity Single Stage Compressor, Continued
Point Name
lonWorks Variable
(NV Index
2
)
SNVT Type
(SNVT Index)
Range/
Default
(in Units)
Heart-
beat
Description
Network Variable Outputs (NVOs)
Unit Status Output
nvoUnitStatus
(15)
SNVT_hvac_status
(112)
No
Reports the unit status. It combines the operating mode,
the capacity of heating and cooling, and any alarms that are
present in the object. The in_alarm member reports the highest
priority current alarm identier.
Unit Status Fields
mode: (see supported modes below)
heat_output_primary: 0 to 100%
heat_output_secondary: 0 to 100%
cool_output: 0 to 100%
econ_output: 0 to 100%
fan_output: 0 to 100%
in_alarm: (see alarm identiers below)
Supported Modes
1 = HVAC_HEAT (Heating Mode)
3 = HVAC_COOL (Cooling Mode)
6 = HVAC_OFF (Inactive Control)
9 = HVAC_FAN_ONLY (Fan Only Mode)
14 = HVAC_DEHUMID (Dehumidication Mode)
Alarm Identiers
0 = No Alarms
1 = Invalid Equipment Cong
2 = Emergency Shutdown
3 = Freeze Fault
4 = EWT Sensor Fail
5 = Room Temp Sensor Fail
6 = IO Expansion Board Com Fail
7 = Condensate Overow
8 = Outdoor Air Temp Sensor Fail
9 = DAT Sensor Fail
10 = BB Serial EEPROM Corrupted
1. Analog Null (0x7FFF) is a discrete temperature value of 621.806ºF/327.67ºC. Its purpose is to indicate a sensor failure condition or when the unit controller is not
using that temperature value.
2. The Network Variable (NV) index number is a unique identier for certain LonWorks variables. Some BAS companies use this numeric value instead of text to
reference these variables. The NV index number can also be found in the XIF le.
3. After Receive Heartbeat is enabled, this variable reverts to the default (non-override) value if it is not refreshed often enough through a network command or if
communication is disabled (i.e. the device is disabled or is ofine).
Table 17: Network Conguration Properties Inputs (NCIs) - Ennity Single Stage Compressor
Point Name
lonWorks Variable
(NV Index
2
)
SNVT Type
(SNVT Index)
Range/
Default
(in Units)
Heart-
beat
Description
Network Conguration Property Inputs (NCIs)
Brownout Reference
Setpoint
nciBrownoutRef UCPTbrownoutRef
25 to 1023 counts
Default: 500
No
Detects a unit controller brownout condition. Brownout
condition occurs when nvoBrownout < 80% of
nciBrownoutRef, and clears when nvoBrownout > 90% of
nciBrownoutRef.
Only perform the calibration procedure if the unit controller
24VAC voltage is within normal operating parameters. A
password of 1023 is required.
Compressor Low
Pressure Alarm Delay
nciLowPresAlmDly UCPTlowPresAlmDly
0 to 120 sec
Default: 30 sec
Unit controller
software v2.9 and
older:
0 to 99 sec
No
Species the time delay between the compressor(s) low
pressure input and alarm generation.
Compressor Low
Suction Temperature
Protection Differential
nciLowTmpProtDif UCPTlowTmpProtDif
2 to 15°F
1.11 to 8.34°C
Default:
8°F / 4.44°C
No
nciLowTmpProtDif is added to the selected Compressor
Low Suction Temperature SP (nciLowTempProt or
nciLowTempProtGL) to determine the setting at which the
alarm clears.
1. Analog Null (0x7FFF) is a discrete temperature value of 621.806ºF/327.67ºC. Its purpose is to indicate a sensor failure condition or when the unit controller is not
using that temperature value.
2. The Network Variable (NV) index number is a unique identier for certain LonWorks variables. Some BAS companies use this numeric value instead of text to
reference these variables. The NV index number can also be found in the XIF le.
3. After Receive Heartbeat is enabled, this variable reverts to the default (non-override) value if it is not refreshed often enough through a network command or if
communication is disabled (i.e. the device is disabled or is ofine).

Table of Contents

Other manuals for Daikin MicroTech III

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin MicroTech III and is the answer not in the manual?

Daikin MicroTech III Specifications

General IconGeneral
BrandDaikin
ModelMicroTech III
CategoryController
LanguageEnglish

Related product manuals