appendIx a: proToCol ImplemenTaTIon ConformanCe sTaTemenTs (pICs)
www.DaikinApplied.com 63 ED 15103-6 • MICROTECH III WSHP UNIT CONTROLLER
Standard Object Types Supported
Object-Type Creatable Deleteable Optional Writeable
Analog Input
COV_Increment, Out_of_Service,
Present_Value, Units
Analog Value
COV_Increment, Present_Value, Priority_Array,
Relinquish_Default, Units
Binary Input
Active_Text, Description, Inactive_Text
Binary Value
Active_Text, Description, Inactive_Text Present_Value
Multi-state Input
State_Text
Multi-state Value
State_Text
Present_Value, Priority_Array,
Relinquish_Default,
MSV15 = Device Units (English – Metric)
Device
Description
Location
Max_Master
Description
Location (Limit 32 Chars)
Max_Master
Data Link Layer Options
BACnet IP, (Annex J)
BACnet IP, (Annex J), Foreign Device
MS/TP master (Clause 9), baud rate(s):
9600, 19200, 38400 & 76800
MS/TP slave (Clause 9), baud rate(s):
9600, 19200, 38400 & 76800
Segmentation Capability
Segmented requests
supported Window Size: 4 for IP and 1 for
MS/TP
Segmented responses
supported Window Size: 4 for IP and 1 for
MS/TP
Device Address Binding
Yes Static Device Binding
No
Character Sets Supported
ANSI X3.4
IBM
®
/Microsoft
®
DBCS
ISO 8859-1
ISO 10646 (UCS-2)
ISO 10646 (UCS-4)
JIS C 6226
NOTE: Support for multiple character sets does not imply
they can be supported simultaneously.

Table of Contents

Other manuals for Daikin MicroTech III

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin MicroTech III and is the answer not in the manual?

Daikin MicroTech III Specifications

General IconGeneral
BrandDaikin
ModelMicroTech III
CategoryController
LanguageEnglish

Related product manuals