ED 15103-6 • MICROTECH III WSHP UNIT CONTROLLER 46 www.DaikinApplied.com
ComprehensIve daTa Tables
Table 20: Network Conguration Properties Inputs (NCIs) - SmartSource Single and Two Stage Compressor and Ennity
Large Two Compressor, Continued
Point Name
lonWorks Variable
(NV Index)
SNVT Type
(SNVT Index)
Range/
Default
(in Units)
Heart-
beat
Description
Network Conguration Property Inputs (NCIs)
Device Software
Identication
(Minor Version)
nciDevMinVer SCPTdevMinVer 0 to 255 No
The software minor version of the communication module
rmware.
Do not modify this conguration property.
Software Jumpers nciSoftJumpers UCPTsoftJumpers 16 Characters No
Sets the software jumper conguration. This property is not
implemented in unit controller software.
Third Stage Heating
Setpoint Differential
nciStg3SptDiff UCPTstg3SptDiff
1 to 10°F
0.55 to 5.56°C
Default:
6ºF / 3.33ºC
No
Used to determine the Third Stage Heating ON setpoints from
the Second Stage ON setpoints for units controlled by room
sensors.
Unit Application
Identication
(Major Version)
nciUnitAppMajVer UCPTunitAppMajVer 0 to 255 No
The major version of the unit controller software.
Do not modify this conguration property.
Unit Application
Identication
(Minor Version)
nciUnitAppMinVer UCPTunitAppMinVer 0 to 255 No
The minor version of the unit controller software.
Do not modify this conguration property.
Unoccupied Setpoint
Differential
nciUnoccDiff UCPTunOccDiff
2 to 10ºF
1.11 to 5.56ºC
Default:
2ºF / 1.11ºC
No
Sets the Unoccupied hysteresis that determines the Effective
OFF setpoints.
Interaction Rule
nciUnoccDiff < (unoccupied_cool – unoccupied_heat)