ED 15103-6 • MICROTECH III WSHP UNIT CONTROLLER 46 www.DaikinApplied.com
ComprehensIve daTa Tables
Table 20: Network Conguration Properties Inputs (NCIs) - SmartSource Single and Two Stage Compressor and Ennity
Large Two Compressor, Continued
Point Name
lonWorks Variable
(NV Index)
SNVT Type
(SNVT Index)
Range/
Default
(in Units)
Heart-
beat
Description
Network Conguration Property Inputs (NCIs)
Device Software
Identication
(Minor Version)
nciDevMinVer SCPTdevMinVer 0 to 255 No
The software minor version of the communication module
rmware.
Do not modify this conguration property.
Software Jumpers nciSoftJumpers UCPTsoftJumpers 16 Characters No
Sets the software jumper conguration. This property is not
implemented in unit controller software.
Third Stage Heating
Setpoint Differential
nciStg3SptDiff UCPTstg3SptDiff
1 to 10°F
0.55 to 5.56°C
Default:
6ºF / 3.33ºC
No
Used to determine the Third Stage Heating ON setpoints from
the Second Stage ON setpoints for units controlled by room
sensors.
Unit Application
Identication
(Major Version)
nciUnitAppMajVer UCPTunitAppMajVer 0 to 255 No
The major version of the unit controller software.
Do not modify this conguration property.
Unit Application
Identication
(Minor Version)
nciUnitAppMinVer UCPTunitAppMinVer 0 to 255 No
The minor version of the unit controller software.
Do not modify this conguration property.
Unoccupied Setpoint
Differential
nciUnoccDiff UCPTunOccDiff
2 to 10ºF
1.11 to 5.56ºC
Default:
2ºF / 1.11ºC
No
Sets the Unoccupied hysteresis that determines the Effective
OFF setpoints.
Interaction Rule
nciUnoccDiff < (unoccupied_cool – unoccupied_heat)