OM 1280-2 • MICROTECH UNIT CONTROLLER 28 www.DaikinApplied.com
Table 11: Occupancy Mode Interactions
Occupancy
Override Input
(MSV7)
LUI OccManCmd
Tenant Override
Active/Inactive
Occupancy
Scheduler Input
(MSV8)
Internal Schedule
Occupancy
Sensor Input
(MSV9)
Hardwired Sensor
Input
Occupancy
Output (MSV6)
1 (Occ) NA NA NA NA NA NA 1 (Occ)
2 (Unoc) NA NA NA NA NA NA 2 (Unoc)
3 (Bypass) NA NA
1 (Occ) NA NA NA 1 (Occ)
2 (Unoc) NA NA NA 3 (Bypass)
3 (Standby) NA NA NA 3 (Bypass)
4 (Null)
Occ NA NA 1 (Occ)
Unoc 1 (Occ) NA 1 (Occ)
Unoc 2 (Unoc) NA 3 (Bypass)
Unoc 3 (Null) NoBI
1
3 (Bypass)
Unoc 3 (Null) Occ
2
1 (Occ)
Unoc 3 (Null) Unoc
3
3 (Bypass)
4 (Standby) NA NA NA NA NA NA 4 (Standby)
5 (Null) Occ NA NA NA NA NA 1 (Occ)
5 (Null) Unoc NA NA NA NA NA 2 (Unoc)
5 (Null) Bypass NA
1 (Occ) NA NA NA 1 (Occ)
2 (Unoc) NA NA NA 3 (Bypass)
3 (Standby) NA NA NA 3 (Bypass)
4 (Null)
Occ NA NA 1 (Occ)
Unoc 1 (Occ) NA 1 (Occ)
Unoc 2 (Unoc) NA 3 (Bypass)
Unoc 3 (Null) NoBI
1
3 (Bypass)
Unoc 3 (Null) Occ
2
1 (Occ)
Unoc 3 (Null) Unoc
3
3 (Bypass)
5 (Null) Standby NA NA NA NA NA 4 (Standby)
5 (Null) Null Inactive
1 (Occ)
NA 1 (Occ) NA 1 (Occ)
NA 2 (Unoc) NA 4 (Standby)
NA 3 (Null) NoBI
1
1 (Occ)
NA 3 (Null) Occ
2
1 (Occ)
NA 3 (Null) Unoc
3
4 (Standby)
2 (Unoc) NA NA NA 2 (Unoc)
3 (Standby) NA NA NA 4 (Standby)
4 (Null)
Occ 1 (Occ) NA 1 (Occ)
Occ 2 (Unoc) NA 4 (Standby)
Occ 3 (Null) NoBI
1
1 (Occ)
Occ 3 (Null) Occ
2
1 (Occ)
Occ 3 (Null) Unoc
3
4 (Standby)
Unoc 1 (Occ) NA 1 (Occ)
Unoc 2 (Unoc) NA 2 (Unoc)
Unoc 3 (Null) NoBI
1
2 (Unoc)
Unoc 3 (Null) Occ
2
1 (Occ)
Unoc 3 (Null) Unoc
3
2 (Unoc)
5 (Null) Null Active
1 (Occ)
NA 1 (Occ) NA 1 (Occ)
NA 2 (Unoc) NA 3 (Bypass)
NA 3 (Null) NoBI
1
1 (Occ)
NA 3 (Null) Occ
2
1 (Occ)
NA 3 (Null) Unoc
3
3 (Bypass)
2 (Unoc) NA NA NA 3 (Bypass)
3 (Standby) NA NA NA 3 (Bypass)
4 (Null)
Occ 1 (Occ) NA 1 (Occ)
Occ 2 (Unoc) NA 3 (Bypass)
Occ 3 (Null) NoBI
1
1 (Occ)
Occ 3 (Null) Occ
2
1 (Occ)
Occ 3 (Null) Unoc
3
3 (Bypass)
Unoc 1 (Occ) NA 1 (Occ)
Unoc 2 (Unoc) NA 3 (Bypass)
Unoc 3 (Null) NoBI
1
3 (Bypass)
Unoc 3 (Null) Occ
2
3 (Bypass)
Unoc 3 (Null) Unoc
3
3 (Bypass)
NOTE: The tenant override is a set of dry contacts placed in parallel with the space temperature sensor (aiSetpointAdjust). When the contacts are closed momentarily, the bypass timer becomes
active and is set to ncpBypassTime, and the unit enters the Bypass mode. The tenant override function is active until the timer expires.