EasyManuals Logo

Daikin MicroTech User Manual

Daikin MicroTech
78 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #32 background imageLoading...
Page #32 background image
OM 1280-2 • MICROTECH UNIT CONTROLLER 32 www.DaikinApplied.com

Table 14: Setpoint Calculation Examples
Example A – Stand-Alone Unit, No remote sensor, No network communication
Given
Occupancy Mode = Occupied and Unit Mode = Heat
Space Temp Setpoint = (not used)
󰀨
Setpoint Shift = (not used) = 0.0°F
OHS = 69.8°F
󰀨
󰀨 󰀨󰀨
= 69.8°F + 0.0°F + 0.0°F + 0.0°F = 69.8°F
Example B – Stand-Alone Unit, Remote sensor with 55ºF – 95ºF Setpoint, No network communication
Given
Occupancy Mode = Occupied and Unit Mode = Heat
Space Temp Setpoint = 71.0°F (from remote sensor)
󰀨
Setpoint Shift = (not used) = 0.0°F
OCS = 75.0°F, OHS = 70.0°F
󰀨
󰀨
󰀨󰀨󰀨
Example C – Stand-Alone Unit, Remote sensor with +/- 5°F, BACnet network communication
Given
Occupancy Mode = Occupied and Unit Mode = Heat
Space Temp Setpoint = 71.0°F (from network input)
󰀨
Setpoint Shift = (from network input) = -2.0°F
OCS = 74.0°F, OHS = 68.0°F
󰀨
󰀨
󰀨󰀨󰀨
Proportional Integral (PI) Control Loops
The MicroTech UVC uses PI-loop control for heating, cooling
and ventilation processes within the unit ventilator. Numerous
PI algorithms can be used depending upon the unit ventilator

Table 15: PI Loop List
PI loops Setpoint
Feedback
(controlled variable)
Output
PI-1 Single Zone VAV Fan 󰀨 Control Temperature Fan Speed
PI-2 Economizer / Free Cooling 󰀨 Discharge Air Temperature Position the OA Damper
PI-3 Modulating Cooling Valve 󰀨 Discharge Air Temperature Modulating Cooling Valve Position
PI-4 Modulating Hot Water Valve 󰀨 Discharge Air Temperature Modulating Hot Water Valve Position
PI-5 Face and Bypass Damper 󰀨 Discharge Air Temperature Face and Bypass Damper Position
PI-6
CO
2
/ Demand Control
Ventilation
󰀨
2
Setpoint Space CO
2
Position the OA Damper
PI-7 DAT Low Limit
󰀨
Setpoint
Discharge Air Temperature Position the OA Damper
PI-8 Electric Heat 󰀨 Discharge Air Temperature Electric Heat Stage

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin MicroTech and is the answer not in the manual?

Daikin MicroTech Specifications

General IconGeneral
BrandDaikin
ModelMicroTech
CategoryFan
LanguageEnglish

Related product manuals