OM 1280-2 • MICROTECH UNIT CONTROLLER 58 www.DaikinApplied.com

Hydronic Water Coil Freeze Stat
Name: WaterCoilFreezeProblemAlarm
Description
Coil Freeze Stat installed, the associated binary input is
open, and the face and bypass damper is enabled. Note: see
WaterCoilFreezeFaultAlarm for fault that occurs when the face
and bypass damper is disabled
Type: Problem
Activate
Freeze Stat installed and the associated binary input is open.
Upon active:
Alarm is indicated on the LUI

FAULTPROB.
LED output alarm indication is activated
OAD closes immediately
Heating EOC Valve opens immediately
Cooling EOC Valve opens immediately
The face and bypass damper is 100% bypass for cooling
or temp OK. (2 position heating valve, 2 position heating
and cooling valve)
The face and bypass damper is 100% bypass for heat
required or temp OK. (2 position cooling valve with no
electric heat)
The face and bypass damper is 100% face if heating is
required. (2 position cooling valve with electric heat)
The face and bypass damper is allowed to modulate if
heating is required. (2 position heating valve, 2 position
heating and cooling valve)
The face and bypass damper is allowed to modulate if
cooling is required. (2 position cooling valve)
The space fan is allowed to run. (All 2 position valves)
The hot/cold water valves are forced to a minimum
position of 50%. If heating or cooling is required, the
valve is allowed to modulate above 50%
Deactivate: Hydronic Water Coil Freeze Stat binary input is
closed.
Reset: Auto
Low Suction Line Temperature
Name: LowSuctionLineTempAlarm
Description: The suction line temperature is below the Low
Suction Line Temperature setpoint.
Type: Problem
Activate
suction line refrigerant temperature sensor and the reading is

is not in the defrost state.
Upon active:
Alarm is indicated on the LUI

FAULTPROB
LED output alarm indication is activated
Deactivate: Indoor air coil/suction line refrigerant temperature

󰀨
Reset: 2 automatic resets in 7 days then a manual clear from
the LUI keypad, network or room sensor is required.
Can’t Cool Failure
Name: CantCoolAlarm
Description: The unit is trying to cool, but conditions do not
allow this (entering water temperature is too high for hydronic

Type: Problem
Activate: All of the following are true:
Cooling is required
Compressor cooling is unavailable.
Entering water temperature is too warm for hydronic
heating
Economizer cooling is unavailable
Upon active:
Alarm is indicated on the LUI

FAULTPROB
LED output alarm indication is activated
Deactivate: Compressor or economizer cooling becomes
available, or the entering water temperature becomes cold
enough to provide cooling.
Reset: Auto