www.DaikinApplied.com 61 OM 1280-2 • MICROTECH UNIT CONTROLLER
Hydronic Water Coil Freeze Fault
Name: WaterCoilFreezeFaultAlarm
Description: Hydronic water coil freeze fault to protect coil
from freezing. Note: see WaterCoilFreezeProblemAlarm
for problem alarm that occurs when the unit has a face and
bypass damper.
Type: Fault
Freeze Stat installed, the associated binary input is open. and
the face and bypass damper is disabled.
Upon active:
• Alarm type is Fault which causes unit shutdown.
•
• Alarm is indicated on the LUI
• Fault relay is energized
• LED output fault indication is activated
• Space fan is immediately de-energized
• Compressor is immediately de-energized
• Outdoor fan is immediately de-energized
• Outside air damper is forced closed
• All electric heat stages are de-energized
• The hot/cold water valves are forced to position of 50%.
Deactivate: Freeze stat input closes
Reset: Auto
Application Conguration Alarm
Name
Description
parameters. This means that multiple, or duplicate, inputs have
Type: Warning
Upon active:
• Alarm is indicated on the LUI
Deactivate: Activate is not Active.
Reset: Auto
Control Board Alarm
Name: ControlBoardAlarm
Description: The application has detected a functional issue
with the control board.
Type: Fault
Activate
is not 0.
Upon active:
• Alarm is indicated on the LUI
• Unit is shut down
Deactivate: Internal application point ControlBoardStatus bit
Reset: Auto (this is not likely to reset as the cause is usually a
hardware problem with the board).