Si20-701_B Troubleshooting by Remote Controller
208
Troubleshooting
Refer to P.473.
The
error is displayed
again.
YES
NO
Is the
electronic
expansion valve
connector properly
connected to the
outdoor unit
PCB?
NO
YES
YES
Connect
properly.
Turn OFF the power
supply and turn the power
ON.
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.
A
Is the coil resistance
of the electronic
expansion valve
normal?
NO
Replace the
electronic
expansion valve
coil.
CHECK 8
CHECK 8