EasyManua.ls Logo

Daikin R35GV1 - P4 Radiation Fin Thermistor Abnormality

Daikin R35GV1
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting by Remote Controller Si20-701_B
331
3.76
P4
Radiation Fin Thermistor
Abnormality
Remote Controller Display
P4
Applicable Models
RZ(Y)
Method of Error Detection
Open circuit or short circuit in radiation fin thermistor is
detected when the compressor is not operating.
Error Decision Conditions
When open circuit or short circuit in radiation fin
thermistor is detected in non-operating compressor
Supposed Causes
Defective thermistor
Defective outdoor unit PCB

Table of Contents

Related product manuals