Troubleshooting by Remote Controller Si20-701_B
369
NO
NO
NO
YES
YES
YES
Recheck for the
power supply. If
there is no
problem with the
power supply,
replace the
noise filter PCB.
If the error
recurs, replace
the inverter
PCB.
Recheck for the
power supply. If
there is no
problem with the
power supply,
replace the
inverter PCB.
If the PCB
replaced is
badly
damaged,
compressor is
likely to get
defective. To
make sure,
recheck the
compressor.
Check the
harness, and
then replace it if
necessary.
End of
measures:
The error may
temporarily
result from on-
site causes.
Causes:
Instantaneous
power failure
(open phase),
noises, or else.
Stop
(standby)
before the fan
rotates.
Stop
(standby) when
the compressor
starts up.
The
"U2" error
recurs.
C
Power
ON
Turn ON the power
supply.