Si20-701_B Troubleshooting by Remote Controller
258
2: “Pressure Sensor”, pressure / voltage characteristics
table.
Detected pressure PH (MPa)
Output voltage V
-0.5
-0.5
0
0.5
1.0
2.0
3.0
1.5
2.5
0.5 1.5 2.5 3.501234
V
DC
PH
PH= 1.38V-0.69
PH: Detected pressure (MPa)
V : Output Voltage (V)