Troubleshooting by Remote Controller Si20-701_B
89
Troubleshooting
Refer to P.459.
Is
there
any foreign
matter around the
fan?
YES
NO
Remove the
foreign matter.
Is
the fan
motor harness
connected to indoor
unit PCB?
NO
YES
Connect
correctly.
With
connector
for fan motor
disconnected, can the
fan be easily turned
by hands?
NO
YES
Replace the fan
motor.
Turn OFF the power
supply. Wait for 10
minutes.
Check for the fan motor
connector.
Is the
resistance
between each pins
above judgement
standard?
NO
YES
Replace the fan
motor.
Replace the
indoor unit PCB.
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.
CHECK 1