Si20-701_B Troubleshooting by Remote Controller
462
For outdoor air thermistor
For suction pipe thermistor
For heat exchanger thermistor
For intermediate heat exchanger thermistor
For liquid thermistor
For remote controller thermistor
T°C k T°C k
-30 361.7719 40 10.6281
-25 265.4704 45 8.7097
-20 196.9198 50 7.1764
-15 147.5687 55 5.9407
-10 111.6578 60 4.9439
-5 85.2610 65 4.1352
0 65.6705 70 3.4757
5 50.9947 75 2.9349
10 39.9149 80 2.4894
15 31.4796 85 2.1205
20 25.0060 90 1.8138
25 20.0000 95 1.5575
30 16.1008 100 1.3425
35 13.0426 105 1.1614
3SA48001 (AD87A001J)