IM 1287-6 • REBEL APPLIED ROOFTOP 146 www.DaikinApplied.com
Altitude Conversion
WARNING
This unit is equipped at the factory for use with either natural gas or propane,
as specied on the furnace data plate. Conversion requires a special kit
supplied by Daikin Applied Parts. Failure to use the proper conversion kit
can cause a re, carbon monoxide poisoning, or explosion which may result
in personal injury, property damage, or death.
WARNING
Installation and maintenance must be performed only by qualied personnel
who are trained and experienced with this type of equipment and familiar
with local codes and regulations.
For elevations up to 2000 feet, rating plate input ratings apply.
For altitudes listed in Table 36, use associated altitude
conversion kit.
For altitudes above 7000 feet, consult Daikin Applied Parts for
required conversion kit.
NOTICE
The furnace is not recommended for installation at altitudes above 11,000
feet.
NOTE: If the fuel source has been derated for altitude by
the local utility provider, then a conversion kit is not
required
See tables below for part numbers. Contact local gas supplier
to conrm gas heating value has been devalued for applicable
elevations.
Table 36: Furnace Identications for Altitude
Elevation in feet Part Number
200 MBH (58.6 KW)
2000–2999 N/A
3000-3999 910333674
4000–4999 910333676
5000–5999 910333677
6000–6999 910333679
400 MBH (117.2 KW)
2000–2999 N/A
3000–3999 910333680
4000–4999 910333682
5000–5999 910333683
6000–6999 910333684
600 MBH (175.8 KW)
2000–2999 N/A
3000–3999 910333685
4000–4999 910333686
5000–5999 910333687
6000–6999 910333688
800 MBH (234.5 KW)
2000–2999 N/A
3000–3999 910333689
4000–4999 910333690
5000–5999 910333691
6000–6999 910333692
1125 MBH (329.7 KW)
2000–2999 N/A
3000–3999 910333693
4000–4999 910333694
5000–5999 910333695
6000–6999 910333696
1500 MBH (439.6 KW)
2000–2999 (2x) 910452264
3000–3999 (2x) 910452266
4000–4999 (2x) 910452268
5000–5999 (2x) 910452270
6000–6999 (2x) 910452272